High temperature Heat Pumps from 17 to 25 kW Installation and user manual 17 / 3 m 17 / 3 m Ref. 151430 17 / 3 t 20 / 3 t 25 / 3 t 17 / 3 t Ref. 151435 20 / 3 t Ref.
• It is FORBIDDEN : 1.4 - Delivery terms and conditions - to operate the Heat Pump using air intake containing solvents or explosive materials. In general, the material is transported at the recipient’s own risk. - to use air intake containing grease, dust, or aerosol particles. It is important to verify that all of the elements have been received - to connect vented exhaust hoods to the appliance.
2 - INTRODUCTION 2.1 - Standard confi gurations Mid-season In cold weather In extreme cold onl y compressor( only compressor ( both compressors is used. is used. ) and ( The fan ( ) runs The fan ( ) runs are used at the same time.
3 - INSTALLATION 3.1 - Installing the HRC The Heat Pump must always be transported in a vertical position, including during installation. It should be transported with the help of a forklift. Do not use the hydraulic connections to move the appliance, take hold of it using the four bottom corners of the appliance.
3.1.1.1 - Heat Pump installation site Always make sure the heat exchanger fi ns are Minimum distances to respect for proper installation of the Heat protected when handling the appliance. Pump: (mm) : The Heat Pump must handled with caution and without being subjected to impacts, especially when placing on the ground.
3.1.1.2 - Condensates drainage 3.1.1.3 - Heater cable for external condensates drainage When the appliance is operating in frost protection mode, the The Heat Pump allows for the addition of an external heater cable condensed water must be drained off . In order for the condensates to prevent freezing of the condensates drainage circuit.
3.2 - Hydraulic installation The Heat Pump is equipped with a hydraulic pressure relief valve set at 2.5 bars. A service 3.2.1 - Hydraulic connections on the installation pressure below this value should be maintained. In order to ensure that fl uids can circulate properly, it is advisable to check that the sizing of piping in the circuit is appropriate between the Heat Pump and the Pilot.
3.2.2 - Hydraulic connections : 3.2.3 - Heat Pump and Pilot pressure-relief valves Heat Pump circuit The Heat Pump and the Pilot are both equipped with pressure- A sufficient flow rate should be ensured so that the range of relief valves. temperature between the outlet and inlet of the Heat Pump does The pressure-relief valve on the Heat Pump sets the maximum not exceed 8°C when the Heat Pump is operating at full power (take...
3.2.5 - Heat Pump water inlet fi lter (supplied) 3.3 - Electrical control connections A fi lter 1’’1/4 must be installed on the water inlet piping on the Heat Pump: 3.3.1 - Connecting to the Heat Pump control • Respect the direction of fl ow on the fi lter (arrow on the valve) 3.3.1.1 - 2-core sheathed cable The Heat Pump is pre-equipped with a non-polarised, 2-core...
Terminal strips 3.4 - Connecting to the power supply The terminal strips are spring-loaded «Cage Clamps». For handling, use the following : - for2,5mm² control terminals or 4mm² - Ensure that the power supply is suffi cient to supply both the Heat 6mm²...
Page 15
The HRC Heat Pump is CE-marked. It is compliant with French standard NF C15-100 as well as European standards EN 61000-3-3 and EN 61000-3-11, among others. It is equipped with a progressive start-up, which limits the current at start-up to 45A in single-phase, and 60A in three-phase. The power supply cable should be sized carefully according to the following factors: - Maximum current required...
3.4.2.1 - HRC Heat Pump : 3.4.3 - Electrical protection for the compressors 230V single-phase connection The HRC Heat Pump is equipped with a progressive start-up device to limit the intensity of the current when the motor starts up, in compliance with the NF C-15-100 standard: 45A per phase in single-phase and 60A per phase in three-phase.
5 - MAINTENANCE AND 4 - SET-UP TROUBLESHOOTING • All work carried out on the hydraulic circuits and the electrical installations must be carried out in compliance with regulations in eff ect in the country of installation, by a qualifi ed professional. •In order to ensure the best performance •...
5.2.2 - Maintenance of the heating circuit 5.4 - Maintenance of the electrical components • Release any trapped air in the HRC Pilot+ • Check that the entire circuit is watertight, including the pressure- relief valves. • Always disconnect the appliance from •...
5.5 - Errors which are not signalled by error message or alert Errors not displayed on the Possible causes Solutions screen place it in winter mode and then auto. connected to the Pilot and the power supply. request configured. Pump (Check that there is voltage and the values: compressor start-up is prevented if voltage is too high or too low.
• Check the power supply to the Heat Pump before and • Start-up process incomplete during start-up. It must not be lower than 200V. 5 flashes Three-phase starter for the HRC70 17kW, 20kW and 25kW three-phase Heat Pump Voyant alarme Causes possibles Actions à mener Flashing •...
Under no circumstances does a defective part warrant the replacement of fl at. the whole appliance. The warranty only applies to parts which we (AUER) identify as having 7.1.2.3 - Installation site been defective at manufacture. If necessary, the part or product should...
A2 - Technical specifi cations A2.1 - General specifi cations single-phase three-phase three-phase three-phase Maximum temperature 70°C 70°C 70°C 70°C R290 refrigerant fl uid 0,900 kg 0,900 kg 0,900 kg 0,900 kg Exterior air Temperature range -20°C +40°C -20°C +40°C -20°C +40°C -20°C +40°C Electrical supply...
A3 - EU declaration A5 - Sizing the expansion vessel This device complies with international electrical safety standards - For a heating installation with radiators: IEC 60335-1, IEC 60335-2-40. The CE marking present on the The expansion vessel equipping the boiler may be suffi cient. device attests to its conformity with the following Community Always check that the capacity of the existing expansion vessel Directives, of which it meets the essential requirements:...
- Protect the installation against corrosion with a corrosion A6 - Treatment of the water in the inhibitor, example: SENTINEL X100. Or against corrosion heating circuit and freezing with an inhibitor with an anti-freeze additive. Example : SENTINEL X500 or SENTINEL R600. •...
Page 30
When using a concentrated protect which needs to be diluted with water, mix the water+anti-freeze+inhibitor mixture together prior to inserting it into the installation. RENDERING THE WARRANTY NULL AND VOID All deterioration of the appliance due to an inappropriate quality of water and/ or the presence of corrosion in the absence of treatment products as described above, and/or an improper purging of air of the installation will...
A7 - Product performances tables A7.1 - HRC Heat Pump 17kW single-phase (Conforms to standard: EU n°811/2013) AUER Marque / Brand name Modèle / Model 17 mono /3 Pompe a chaleur Air- Eau / Air- Water heat pump Type / Type Classe d'efficacité...
A7.2 - HRC Heat Pump 17kW three-phase (Conforms to standard: EU n°811/2013) AUER Marque / Brand name Modèle / Model 17 tri /3 Type / Type Pompe a chaleur Air- Eau / Air- Water heat pump Classe d'efficacité énergétique chauffage / Heating seasonnal energy efficiency class...
A7.3 - HRC Heat Pump 20kW three-phase (Conforms to standard: EU n°811/2013) AUER Marque / Brand name Modèle / Model 20 tri /3 Type / Type Pompe a chaleur Air- Eau / Air- Water heat pump Classe d'efficacité énergétique chauffage / Heating seasonnal energy efficiency class...
A7.4 - HRC Heat Pump 25kW three-phase (Conforms to standard: EU n°811/2013) AUER Marque / Brand name Modèle / Model 25 tri /3 Type / Type Pompe a chaleur Air- Eau / Air- Water heat pump Classe d'efficacité énergétique chauffage / Heating seasonnal energy efficiency class...
A8 - Electricity provider information form This form is to given to the electricity provider for all preliminary evaluation for the installation of an HRC Heat Pump in case of an insuffi cient power grid. This table contains information on both electrical and technical data about the HRC Heat Pump. This technical data is provided in the table §...