Chapter 4
[AH-01]~[AH-06]
PID1 function
Code/Name
AH-01
PID1 enable
02(Enable:inverted output)
・Validates the PID1 operation.
・If [AH-01]=01 when the PID output reaches negative
value, the PID output is limited to 0.
・If [AH-01]=02 when the PID output reaches negative
value, the PID output lets out an inverted output.
・When the PID output is negative, the motor will rotate
in the contrary direction.
・If [PID] terminal is ON, the PID control is disabled and
the [PID] target value becomes the frequency
reference.
Code/Name
AH-02
PID1 deviation inverse
+
PID target value
-
Feedback
+
Code/Name
AH-03
unit selection for PID1
AH-04
PID1 adjustment (0%)
AH-05
PID1 adjustment
(100%)
AH-06
PID1 Adjustiment
(decimal point)
・The unit and display data related to the output of the
PID control can be changed.
Multistage target 1~15
09
PID1 target [AH-10]
01
Analog input 1
02
[AH-07]
Analog input 2
03
Analog input 3
10
RS485
communication
11
Option 1
12
[AH-42]
Option 2
13
Option 3
09
PID1 target [AH-44]
00
Not used
Range (unit)
Initial value
00(Disable)/
01(Enable)/
00
Range (unit)
Initial value
00(Disable)/
00
01(Enable)
Reverse PID1
[AH-02]
-
00
PID
01
operation
Initial
Range (unit)
value
<unit table> at the end
of the document can
01
be consulted
-10000~10000
-10000~10000
10000
0~4
PID1
target value
[SVC1-4]
01
[AH-50]
+, -, x, ÷
00
For parameter configuration
Code/Name
AH-07
Target value 1 reference
selection for PID1
AH-10
PID1 target value-1
AH-12
PID1 Multistage set point 1
AH-14
PID1 Multistage set point 2
AH-16
PID1 Multistage set point 3
AH-18
PID1 Multistage set point 4
AH-20
PID1 Multistage set point 5
AH-22
PID1 Multistage set point 6
AH-24
PID1 Multistage set point 7
AH-26
PID1 Multistage set point 8
AH-28
PID1 Multistage set point 9
AH-30
PID1 Multistage set point 10
AH-32
PID1 Multistage set point 11
AH-34
PID1 Multistage set point 12
AH-36
PID1 Multistage set point 13
AH-38
PID1 Multistage set point 14
AH-40
PID1 Multistage set point 15
AH-42
Input source selection of Set
point 3 for PID1
AH-44
PID1 target value-2
AH-46
Target value 3 reference
selection for PID1
AH-48
PID1 target value-3
0
AH-50
Math operator selection of
PID1 target value 1
2
*1) Display range can be set by [AH-04], [AH-05] and [AH-06].
*2) 00 (Not use) /01 (Setting by Terminal [Ai1]) /02 (Setting by Terminal[Ai2]) /03
(Setting by Terminal [Ai3]) /04 (Setting by Terminal [Ai4])/05 (Setting by Terminal
[Ai5]) /06 (Setting by Terminal [Ai6]) /07(Setting by parameter) /08 (Setting by RS485)
/09 (Option-1) /10(Option-2) /11 (Option-3) /12 (Pulse train input(internal)) /13
(Pulse train input(Option))
・For PID1 target value, two targets are selected, target value 1 and target value 2, the
result of the operation carried out between these two targets constitutes the PID1
target value.
・If Input terminal function 051[SVC1]~054[SVC4] are used, the PID target value can be
changed for the Multistage.
Multistage value
Target value 0
Target value 1
Target value 2
Target value 3
Target value 4
Target value 5
Target value 6
Target value 7
Target value 8
Target value 9
Target value 10
Target value 11
Target value 12
Target value 13
Target value 14
Target value 15
4-18
[AH-07]~[AH-50]
Range (unit)
00~13 *2)
-100.00~100.00(%)
*1)
00~13*2)
-100.00~100.00(%)
00~13*2)
-100.00~100.00(%)
01(Addition)
02(Subtraction)
03(Multiplication)
04(Division)
05(Minimum
deviation)
06 (Maximum
deviation)
SVC4
SVC3
SVC2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
Initial
value
07
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
00
0.00
0.00
0.00
00
SVC1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON