D9412Gv3/D7412Gv3 Responses To Missing Point Conditions; D8125 And D9127 Popit Modules - Bosch D9412GV3 Operation And Installation Manual

Hide thumbs Also See for D9412GV3:
Table of Contents

Advertisement

.
Table 12:
Off-Board Point Errors
Error Condition
+/- leg of the data expansion bus has a
short circuit to earth ground, with
Ground Fault Detect enabled
+/- leg of the data expansion bus is
disconnected
Data expansion bus has a short circuit
+/- leg of the data expansion bus has a
short circuit to the Common terminal on
the control panel
Terminal 26, 28, or 94 has a short
circuit to a Common terminal
Terminal 25, 27, or 94 has a short
circuit to a Common terminal
Terminals 27 and 28 have a short
circuit together
9.1.5
D9412GV3/D7412GV3 Responses to
Missing Point Conditions
The D9412GV3 and D7412GV3 respond to missing
point conditions based on the point's programming
and the armed state of the point's area. For example,
if an interior motion detector point is missing during a
disarmed state, a Missing Trouble event is generated;
however, if the point is missing while the area is
Master Armed, a Missing Alarm event is generated.
Non-fire, 24-hour points always generate a Missing
Alarm event, whereas Fire points always generate a
Missing Fire Trouble event.
9.2

D8125 and D9127 POPIT Modules

D9127 POPITs use the D8125 POPEX Module to
report to the control panel. Each D8125 supports up
to 119 POPIT points. Connect two D8125 Modules to
the D9412GV3 to bring the combined total number of
POPIT and on-board points to 246.
Points 9 to 127 connect to the first POPEX
Module.
Points 129 to 247 connect to the second POPEX
Module.
The D9412GV3 reserves Points 128 and 248 for
internal use.
The control panel annunciates activity only for each
POPIT, not for each detection device connected to
the sensor loop.
Bosch Security Systems, Inc. | 10/10 | F01U143070-03
D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0
Result
Ground Fault event
All POPITs beyond the
disconnection send Missing
report
All POPITs send Missing
report
Pt Bus Trouble event
All POPITs send Missing
report
Pt Bus Trouble event
No Pt Bus Trouble event occurs
Pt Bus Trouble event
Keypad displays:
SERVC ZONEX 1
Pt Bus Trouble event
Keypad displays:
SERVC ZONEX 1
Additional Information
When the data expansion bus restores, Pt
Bus Restore event occurs. If any POPIT is
connected to the data expansion bus
without an assigned Point Index, an Extra
Point event occurs.
The D9127 Module enclosures are made of UL Listed
fire resistant material. D9127T Modules contain
tamper switches. D9127U Modules include
untampered covers. Unless the module is mounted in
a tampered enclosure, UL requires D9127T Modules
for certificated accounts.
Listings
The D8125 POPEX and the D9127 POPIT Modules
are UL Listed for Local or Police Connected Burglar
Alarm, Central Station Burglar Alarm, Household
Burglar Alarm, Central Station Fire, Local Fire,
Remote Station Fire, Household Fire, and Electrically
Actuated Transmitter Applications.
Refer to the D9412GV3/D7412GV3 Approved
Applications Compliance Guide (P/N: F01U143069) to
determine the required equipment and enclosures for
the application.
Off-Board Points
37