Gree 4LIV30HP230V1A Service Manual page 62

Table of Contents

Advertisement

9. Maintenance
Service Manual
3. High temperature and overload protection (E8)(AP1 below means control board of outdoor unit)
Main detection points:
(1) outdoor temperature (2) fan (3)air inlet and air outlet of indoor/outdoor unit
Malfunction diagnosis process:
Installation and Maintenance
Overload protection,
high temperature
prevention protection
Is the outdoor ambient temperature
higher than 53℃?
N
After the complete unit is disconnected
from the power for 20mins
Is the radiation of indoor unit
and outdoor unit is not good?
N
Check whether the outdoor
fan operates normally?
Y
Replace the control board
End
Normal protection. Please operate
it when the outdoor ambient
Y
temperature is improved.
Improve the unit's
Y
radiation environment.
Check whether the fan terminal
N
OFAN is connected well;
Measure any two terminal with
the ohmmeter and resistance is less
than 1000ohm.
Replace the fan capacitor C1
Replace the outdoor fan