Lennox LGT156H Installation Instructions Manual page 61

Table of Contents

Advertisement

HEATING, VENTILATION & SMOKE MINIMUM AND MAXIMUM CFM
Tons
Model
LGT156H Low
13
Std
Med
LGT156H All
15
LGT180H Low
Std
Med
High
LCT180H
15,30,45,60kW
17.5
LGT210H Low, Std, Med
High
LCT210H
15,30,45,60kW
90kW
20
LGT240H Low, Std, Med
High
LCT240H
15,30,45,60kW
90kW
25
LGT300S
Low, Std, Med
High
LCT300S
15,30,45,60kW
90kW
*Use highest value between Heating and Cooling High CFM Max.
TABLE 19
COOLING MINIMUM AND MAXIMUM CFM
Cool 1 CFM
LGT/
Cooling Low CFM
LCT
De­
Unit
Min
Max
fault
156H
3380
1500
6250
180H
3900
2000
7200
210H
4550
2500
8400
240H
5200
3000
9600
300S
6500
3500 12000
*Use Cooling High CFM Max.
Set Minimum Position 2
Use the following mobile service app menu in the Unit
Controller to set "Min OCP Blwr Low" for the blower CFM
below the "midpoint" CFM. When navigating into this
menu, the Unit Controller will run damper calibration and
allow damper position adjustment.
RTU MENU > SETTINGS > RTU OPTIONS > DAMPER
Tap "Next" to skip tabs and complete damper position
calibration until "Damper Calibration Blower Speed High"
tab appears.
Measure the intake air CFM. If the CFM is lower than the
design specified CFM for ventilation air, use the Unit
Controller to increase the damper percent open. If the
CFM is higher than specified, decrease the damper
percent open.
Unit
Speed
Heat Code
L
S
M
N, E, J, K, L
L
S
M
H
N, E, J, K, L
L, S, M
H
N, E, J, K, L
P
L, S, M
H
N, E, J, K, L
P
L, S, M
H
N, E, J, K, L
P
Cool 4 CFM
Cooling High CFM
Default
Min
5200
4000
5400
5000
6300
6000
7200
6250
9000
7000
TABLE 18
Heating CFM
De­
Min
Max
fault
5200
2725
6250
4325
4500
5200
6000
2725
7200
4325
4500
5125
5200
7000
4500
8400
5125
5200
6000
8000
4500
9600
5125
5200
6000
10000 4500
5125
5200
6000
Note - Intake air CFM can also be determined using the
outdoor air temperature, return air temperature and
mixed air temperature. Refer to the economizer or
outdoor air damper installation instructions.
E-Inverter Bypass Option
Max
The supply air inverter is factory-set to by-pass the
6250
inverter manually. To by-pass the inverter and operate the
7200
blower in the constant air volume mode, use the following
8400
Unit Controller menu and set to "engaged":
9600
SETTINGS > RTU OPTIONS > BLOWER > VFD
12000
To configure the unit to by-pass the inverter automatically,
use the following Unit Controller menu.
Press SAVE until the menu reads:
Change the 6
bypass option.
Press SAVE
Caution - Units not equipped with an inverter will have the
th
6
character set to N, indicating the inverter is not
bypassed. The blower motor could be damaged and/or
result in product or property damage if the setting is
changed to automatic or manual.
Page 61
Vent CFM
De­
De­
Min
Max
fault
fault
5200
1950
5200
6000
2250
6000
7000
2625
7000
8000
3000
8000
10000 3750
10000 3750 12000
BYPASS
SETUP > INSTALL
CONFIGURATION ID 1
th
character position to A for automatic
508288-01
Smoke CFM
Min
Max
1950
6250
2250
7200
2625
8400
3000
9600
9/2022