Safety Devices - Immergas VICTRIX 20 Plus Manual

Condensation-type wall-hung room sealed fan-assisted boiler for central heating only or with an external storage tank

Advertisement

Technical Documentation
Heating temperature range
switch
(CM2)
Central heating power
trimmer.
(HEATING POT.)
Fan speed trimmer
(FAN SPEED POT.)
Circulator antilock
Failed ignition lock
Water overtemperature lock
Fume overtemperature lock
Post-circulation pump
Sealed-chamber post-
ventilation
NTC sensor breakage
(B1 and B4)
STVP ed 02/06
Depending on its position, it enables the heating potentiometer to adjust
the temperature between 25ºC and 85ºC (range 1) or between 25ºC and
45ºC (range 2).
This trimmer is used to regulating power during the heating phase, adapting it to system require-
ments (from max set on fan speed trimmer to related minimum).
This regulates top fan speed and adapts it to flue accessory requirements in order to use nominal
heat power.
After each adjustment, the minimum speed is automatically adapted so as to maintain the modula-
tion range unaltered (depending on boiler power).

Safety devices.

The circulator is started for 60 seconds after:
- 24 hours of inactivity with the SUM/WIN switch on SUMMER
- 3 hours of inactivity with the SUM/WIN switch on WINTER (radiator antifreeze).
If, within 10 seconds from the start of the ignition cycle, the ionisation electrode (E3) fails to detect
the flame on the burner, the control unit (IGN BOARD) sends a signal to the modulating control
board (flame lock). This blocks boiler operation and the alarm is shown on the boiler panel display
with error code 01.
To restore boiler operation it must be reset manually by pressing push button PU1.
If the water overtemperature thermostat contact opens (primary circuit temperature higher than
100°C), boiler operation is blocked. When this safety device triggers it is shown on the boiler panel
display with error code 02.
To restore boiler operation it must be reset manually by pressing push button PU1.
If the fume overtemperature thermostat contact opens (condensation module external temperature
higher than 100 °C) due to burning impurities settled on the exchanger (soots, oxidations and so on),
the functioning of the boiler will be blocked.
When this safety device triggers it is shown on the boiler panel display with error code 02.
To restore boiler operation it must be reset manually by pressing push button PU1.
To prevent the water/gas exchanger from overheating, at the end of every heating (opening of the room
thermostat), antifreeze or chimneysweep request, the circulator is kept running for 60 seconds.
After the burner has been switched off, at the end of any type of request, the combustion chamber
is washed and the fan works for 50 seconds at a speed equal to half the set maximum.
The breakage of the d.h.w. sensor (B4) prevents operation in the d.h.w. phase.
Triggering is indicated by error code 12 on the boiler panel display.
The breakage of the heating sensor (B1) prevents operation in both the heating and d.h.w. modes.
Triggering is indicated by error code 05 on the boiler panel display.
24
Technical Documentation
Engaged = Range 1
Not engaged = Range 2