Analog input 60 [mA] states the voltage
value on terminal 60.
Pulse reference [Hz] P states a pulse frequency in
Hz connected to terminal 17 or terminal 29.
External reference [%] gives the sum of the external
references as a percentage (the sum of analog/pulse/
serial communication) in the range from Minimum
reference, Ref
to Maximum reference, Ref
MIN
Heat sink temp. [°C] states the present heat sink
temperature of the VLT AFD. The cut-out limit is 90
± 5°C; cutting back in occurs at 60 ± 5°C.
LCD display text shows the text programmed in
parameter 533 Display text 1 and 534 Display text
2 via the serial communication port.
008 Small display readout 1.1
(SMALL READOUT 1)
Value:
See parameter 007 Large display readout
Reference [Unit]
Function:
This parameter enables a choice of the first of three data
values to be shown on the display, line 1, position 1.
This is a useful function, when setting the PID regu-lator
to see how the process reacts to a change of reference.
For display read-outs, press the [DISPLAY/STATUS]
button. Data option LCP display text [27] cannot
be selected with small display readout.
Description of choice:
There is a choice of 26 different data values, see
parameter 007 Large display readout .
009 Small display readout 1.2
(SMALL READOUT 2)
Value:
See parameter 007 Large display readout
Motorcurrent [A]
Function:
See the functional description for parameter
008 Small display readout.
MG.40.A7.22 - VLT is a registered Danfoss trademark
Description of choice:
There is a choice of 26 different data values, see
parameter 007 Large display readout .
010 Small display readout 1.3
(SMALL READOUT 3)
.
MAX
Value:
See parameter 007 Large display readout
Power [HP]
Function:
See the functional description for parameter
008 Small display readout.
Description of choice:
There is a choice of 26 different data values, see
parameter 007 Large display readout .
[2]
011 Unit of local reference
(UNIT OF LOC REF)
Value:
Hz (HZ)
% of output frequency range (%) (% OF FMAX)
Function:
This parameter decides the local reference unit.
Description of choice:
Choose the required unit for local reference.
012 Hand start on LCP
(HAND START BTTN)
Value:
Disable (DISABLE)
Enable (ENABLE)
Function:
This parameter allows selection/deselection of the
[5]
Hand start key on the control panel.
Description of choice:
If Disable [0] is selected in this parameter, the
[HAND START] key will be inactive.
®
VLT
4000 VT
[6]
[0]
[1]
[0]
[1]
65