Technical specifications
Article number
Number of IO modules
I/O address area
•
Inputs
Outputs
•
per integrated IO subsystem
–
Inputs (volume)
Outputs (volume)
–
Subprocess images
•
Number of subprocess images, max.
Hardware configuration
Number of distributed IO systems
Number of DP masters
•
integrated
Via CM
•
Number of IO Controllers
integrated
•
•
Via CM
PtP CM
•
Number of PtP CMs
Time of day
Clock
•
Type
Backup time
•
•
Deviation per day, max.
Operating hours counter
•
Number
Clock synchronization
•
supported
•
to DP, master
•
in AS, master
•
in AS, slave
on Ethernet via NTP
•
Digital inputs
integrated channels (DI)
Digital inputs, parameterizable
68
6ES7615-4DF10-0AB0
16 384; max. number of modules / submodules
32 kbyte; All inputs are in the process image
32 kbyte; All outputs are in the process image
32 kbyte; Max. 32 KB via X150; max. 8 KB via X160 or X126
32 kbyte; Max. 32 KB via X150; max. 8 KB via X160 or X126
32
64; A distributed I/O system is characterized not only by the integra
tion of distributed I/O via PROFINET or PROFIBUS, but also by the con
nection of I/O via AS-i master modules or links (e.g. IE/PB-Link)
1
Expansion via CMs / CPs (PROFIBUS, PROFINET, Ethernet) not pos
sible; these CMs / CPs can only be operated in a central rack
2
Expansion via CMs / CPs (PROFIBUS, PROFINET, Ethernet) not pos
sible; these CMs / CPs can only be operated in a central rack
The number of connectable PtP CMs (distributed) is only limited by
the number of available slots
Hardware clock
6 wk; At 40 °C ambient temperature, typically
10 s; Typ.: 2.4 s
16
Yes
Yes
Yes
Yes
Yes
28; max. depending on parameterization
Yes; 12 DI, 8 DI/DQ (X122/X132, SINAMICS Integrated) + 8 DI/DQ
(X142, PLC)
6ES7615-7DF10-0AB0
SIMATIC Drive Controller
Equipment Manual, 11/2022, A5E46600370-AC