Download Print this page

ABB ACS850 Quick Start Up Manual page 11

Standard control program
Hide thumbs Also See for ACS850:

Advertisement

Quick Start-up Guide for ACS850 with Standard Control Program 11
The STANDSTILL ID run should be selected only if
the Normal or Reduced ID run is not possible due to
the restrictions caused by the connected mechanics
(e.g. with lift or crane applications).
Notes:
• The motor shaft must NOT be locked and the load
torque must be < 20% during Normal or Reduced
ID run. With permanent magnet motor this
restriction also applies when Standstill ID run is
selected.
• Mechanical brake is not opened by the logic for
the ID run.
• The ID run cannot be performed if parameter
99.05 Motor ctrl mode = Scalar.
Start the motor (by pressing the START button) to
activate the ID run.
ID run is indicated by alarm ID-RUN on the panel
display.
After the text "Done OK" appears on the control panel, press OK to complete the
firmware assistant.
3 – Start/Stop configuration
In the Main menu, highlight ASSISTANTS and press
ENTER.
Highlight Firmware assistants and press SEL.
Highlight Start/Stop Control and press OK.
The following parameters will be set.
Note: Depending on the selections you make, the
routine may skip some of the parameters listed
below.
Select the start/stop function and signal sources for
external control location 1 (EXT1). First, program
parameter 10.01 (start function), then 10.02 and
10.03 to choose the sources of the start signal.
The choices for parameter 10.01 are:
In1: The signal defined in parameter 10.02 is the
source for the start signal (0 = Stop, 1 = Start).
Alarm: ID-RUN
LOC
MAIN MENU
PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT
LOC
ASSISTANTS
Firmware assistants
Application assistant
EXIT
LOC
CHOICE
Select assistant
Motor
Set-upMotor
Start/Stop Control
EXIT
10.01 Ext1 start func
10.02 Ext1 start in1
10.03 Ext1 start in2
1
ENTER
1
SEL
OK

Advertisement

loading