21 Configuration
21.1 Field setting
Installer and user reference guide
78
Make the following field settings so that they correspond with the actual
installation setup and with the needs of the user:
▪
Wireless remote controller address (if applicable)
▪
Ceiling height
▪
Airflow rate when thermostat control is OFF
▪
Time to clean air filter
▪
Number of the connected indoor units as simultaneous operation system
▪
Simultaneous operation system individual setting
▪
T1/T2 input setting
INFORMATION
▪
The connection of optional accessories to the indoor unit might cause changes to
some field settings. For more information, see the installation manual of the
optional accessory.
▪
Following setting are only applicable when using the BRC1H52* user interface.
When using any other user interface, see the installation manual or service
manual of the user interface.
Setting: Wireless remote controller address (if applicable)
When using wireless remote controller, set the wireless remote controller address.
Refer to the installation manual of the connected wireless remote controller.
Setting: Ceiling height
This setting must correspond with the actual distance to the floor and the capacity
class.
If the distance to the floor is (m)
FHA35~71
≤2.7
2.7<x≤3.5
Setting: Airflow rate when thermostat control is OFF
This setting must correspond with the needs of the user. It determines the fan
speed of the indoor unit during thermostat OFF condition.
1 If you have set the fan to operate, set the airflow rate speed:
If you want...
Fan operation during
thermostat OFF
(cooling/heating
operation)
FHA100~140
≤3.8
3.8<x≤4.3
Normal
Stop
ThenFN
M
SW
13 (23)
0
(1)
Then
M
SW
11 (21)
2
Split system air conditioner
4P708119-1 – 2022.11
—
01
02
—
01
02
FHA-A(9)