3.4.3 Water connection

Cabinet bottom view
The water return (3) and supply (4) connections are located under the bottom plate of the
cabinet. During transport, the water connections are protected by an angled sheet metal (2).
To remove the sheet metal and access the water connections you have to remove the lower
side panels (1).
The required connection nominal widths and the position of the connections
at the cabinet's bottom plate can be found in the drawings in the appendix to
this manual.
Condensate drain:
The bottom of the cooling module is designed as a condensate tray with a 10 mm hose
connection (5) at the rear side. By default, the hose connection is closed by a plug.
Especially at low water inlet temperatures it is recommended to realize the condensate drain
on site via the hose connection (5).
Connect the water supply, water return and condensate drain according to the drawings in
the appendix to this operating manual.