Burner Settings - UTICA BOILERS SFH Series Installation, Operation & Maintenance Manual

Water oil fired cast iron boiler
Table of Contents

Advertisement

BOILER
BURNER
MODEL
MODEL
3085
EZ-1HP
3100
EZ-1HP
4100
EZ-1HP
4125
EZ-1HP
4145
EZ-1HP
5160
EZ-2HP
5185
EZ-2HP
6175
EZ-2HP
6210
EZ-2HP
Above settings are preliminary settings only� Final adjustments must be made using combustion test instruments
as previously outlined in the Operating Instructions

15 - BURNER SETTINGS

TABLE 5 - CARLIN EZ-1/2 SETTINGS
FIRING
NOZZLE
RATE
MFR.
0�85
DELAVAN
0�75 x 70 B
1�00
DELAVAN
0�85 x 70 B
1�00
DELAVAN
0�85 x 70 B
1�25
DELAVAN
1�00 x 70 B
1�45
DELAVAN
1�20 x 70 B
1�60
DELAVAN
1�35 x 70 B
1�85
DELAVAN
1�50 x 70 B
1�75
DELAVAN
1�50 x 60 B
2�10
DANFOSS
1�75 x 70 AS
NOZZLE
PUMP
TYPE
PRESSURE
[PSI]
130
140
140
155
145
140
155
140
145
26
HEAD
AIR BAND
BAR
SETTING
0�75
45%
0.85/1.00
55%
0.85/1.00
52%
0.85/1.00
70%
1.10/1.25
78%
0.85/1.00
20%
1�50
30%
1�50
35%
1.65/1.75
65%
P/N 240009735, Rev. G [09/30/2016]
AIR
SHUTTER
BLANK
BLANK
BLANK
BLANK
BLANK
3 SLOT
3 SLOT
3 SLOT
OPEN

Advertisement

Table of Contents
loading