Table of Contents

Advertisement

6. INSTALLATION

These models are designed to be installed hanging from the ceiling or located behind a false ceiling. It is mandatory to
distribute the unit weight between the 4 supports existing in the units:
Using studded rods (ø8 mm x 4), it can be secured to the ceiling and levelled:
Distance between supports (mm):
Model
A
SLIM 800
1652
SLIM 1200
1652
SLIM 1600
1652
SLIM 2000
1952
The installer must ensure that the ceiling structure and the securing elements can bear the weight of the device, taking
into account that it is a dynamic load. To prevent the transmission of vibrations, it is necessary that the installer use
specific isolation elements such as anti-vibrations elements and flexible connection between the unit and the ducts.
Weight
Model
(kg)
SLIM 800
172
SLIM 1200
231
SLIM 1600
266
SLIM 2000
315
* These KITs include 4 x anti-vibrations pads.
B
1124
1604
1804
1804
Recommended
antivibration hangers KIT*
5130064900 KIT AM COMPACT/SLIM
5130064900 KIT AM COMPACT/SLIM
5130064900 KIT AM COMPACT/SLIM
5130064900 KIT AM COMPACT/SLIM
A
Recommended
fl exible connection
5132810200 IAE-200
5132811000 IAE-225
5132813600 IAE-285
5132814400 IAE-315
7