Connection - Psm - D+H CPS-M Series Original Instructions Manual

Table of Contents

Advertisement

Connection – PSM
X2
X4
X5
X6
X2.1
X2.4
X4
X5.1
X5.2
X6.1
X6.2
99.827.31 2.3/08/22
+
+
Output: 24 V DC
PS-1-24-20/40
Input: 230 V AC, 50 Hz
L
N
L
N
PE
230 V AC, 50 Hz
Separate power circuit.
Identify the fuse.
Do not reverse L+N!
Connect PE
No.
Name
Description
X2.1
N+
Output potential without an emergency supply for
ventilation functions, max. 500 mA
X2.2
-
Reference potential (do not connect to P-)
X2.3
+
Output potential with an emergency supply, max.
500 mA
X2.4
-
Reference potential (do not connect to P-)
X4
TCSU1
RJ12 connection of external battery temperature
sensor
X5.1
BATT+
Secondary power supply (battery),
max 40 A
X5.2
BATT-
X6.1
SNT+
Primary power supply (power pack),
max 40 A
X6.2
SNT-
X6
1
2
+
Battery
English
1
2
3
4
X2
PSM-1-24-040
X5
X4
RJ12
1
2
+
Battery
TCSU1-RJ12
CPS-M1
11/36

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cps-m1Cps-m1-060-bCps-m1-s

Table of Contents