Trane Symbio 210 Installation, Operation And Maintenance Manual page 52

Programmable bacnet controller for variable-air-volume vav units
Table of Contents

Advertisement

Calibration, Operation Modes, and Control
Table 17. Local heat only with parallel fan present (continued)
Configuration
Local
Fan and On/Off electric
Not applicable
(1 to 3 stages)
Fan and On/Off hot
Not applicable
water (1 to 3 stages)
Fan and Modulating hot
Not applicable
water
On/Off Electric Reheat
The Airflow Setpoint Minimum Local Heat is enforced during reheat.
When reheat is de-energized, the cooling Airflow Minimum Setpoint is enforced. Refer to and .
Hot Water Heat
Two types of control of hydronic heat are supported:
52
Remote
Parallel Fan
Parallel Fan
Parallel Fan
Parallel Fan
Stage 1; energizes when the space temperature falls below the active heating setpoint and
minimum airflow requirements are met. When the zone temperature rises above the active heating
setpoint by 0.5°F (0.28°C), stage 1 is de-energized.
Stage 2; energizes when the space temperature is 1°F (0.56°C) or more below the active heating
setpoint, and is de-energized when the space temperature is 0.5°F (0.28°C) below the active
heating setpoint.
Stage 3; energizes when the zone temperature is 2°F (1.11°C) or more below the active heating
setpoint, and de-energizes when the space temperature is 1.5°F (0.83°C) below the active heating
setpoint.
ON/OFF
Method of Control
Stage 1
Local thermostatic:
Local thermostatic:
On: Zt < HSP
On: Zt <HSP - 1°F
(0.56°C)
Off: Zt ≥ HSP + 0.5
°F (0.28°C)
Off: Zt ≥ HSP - 0.5°
F (0.28°C)
Each stage
Each stage represents an equal percentage of
represents an
total capacity.
equal percentage
Total capacity is limited by communicated
of total capacity.
supply heat control.
Total capacity is
limited by
communicated
supply heat
control.
Local thermostatic:
Local thermostatic:
On: Zt < HSP
On: Zt <HSP - 1°F
(0.56°C)
Off: Zt ≥ HSP + 0.5
Off: Zt ≥ HSP - 0.5°
°F (0.28°C)
F (0.28°C)
Total capacity is limited
Total capacity is limited
by communicated
by communicated
supply heat control.
supply heat control.
Local PI capacity
Local PI capacity loop.
loop.
Modulating valve capacity = Total capacity.
Modulating valve
Valve drive incrementally open/closed.
capacity = Total
Total capacity limited by communicated supply
capacity.
heat control.
Valve drive
incrementally
open/closed.
Total capacity
limited by
communicated
supply heat
control.
Stage 2
Stage 3
Local thermostatic:
On: Zt < HSP - 2°F
(1.11°C)
Off: Zt ≥ HSP - 1.5°
F (0.83°C)
Not applicable
Not applicable
BAS-SVX091A-EN