Appendix
A
Specifications
See page A-6 for a list of agency approvals for environmental service
and safety.
Physical
Enclosure dimensions
(actual – see ―Panel Cutout‖
in chapter 3 for cutout dimensions)
Bezel dimensions
Weight
DC Power
Input Voltage
Power Dip Tolerance
Insulation Resistance
Real Power
Power Supply Conductor Size
Connector (Vendor, p/n)
GFK-2306E
Height: 8.93 in (226.8 mm)
Width: 11.85 in (301.1 mm)
Depth: 2.37 in (60.1 mm)
Height: 10.34 in (262.6 mm)
Width: 13.26 in. (336.8 mm)
Depth: 0.38 in (9.7 mm)
5.2 lb (2.36 kg)
12 VDC (@ ±20% regulated power supply); or
24 VDC (@ ±20% regulated power supply)
-30% nominal input voltage, 10msec.
>200Mohm @ 1000V frame ground to 0V
>200Mohm @ 1000V frame ground to 24
36W
12 to 18 AWG
For compliance to CE Mark, the isolated frame
ground must be connected.
Recommended frame ground connection is via the
shortest possible route, using 14 AWG.
1777992
Phoenix Contact,
1
A-