Note On Adding Refrigerant - Airwell HDMB-025N-09M22 User & Installation Manual

Table of Contents

Advertisement

Available languages

Available languages

Note on Adding Refrigerant

Some systems require additional charging depending on pipe lengths. The standard pipe length varies
according to local regulations. For example, in North America, the standard pipe length is 7.5m (25').
In other areas, the standard pipe length is 5m (16'). The refrigerant should be charged from the service
port on the outdoor unit's low pressure valve. The additional refrigerant to be charged can be
calculated using the following formula:
Connective Pipe
Air Purging
Length (m)
Method
< Standard pipe length Vacuum Pump
> Standard pipe
Vacuum Pump
length
CAUTION
DO NOT
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Liquid Side: Ø 6.35 (ø 0.25")
R32:
(Pipe length – standard length) x 12g/m
(Pipe length – standard length) x 0.13oZ/ft
mix refrigerant types.
Additional Refrigerant
N/A
Liquid Side: Ø 9.52 (ø 0.375")
(Pipe length – standard length) x 24g/m
(Pipe length – standard length) x 0.26oZ/ft
R32:
Page 34