Download Print this page

Component Identification; Connection Diagram; Wiring Instructions - M-system R7M-EC8B Instruction Manual

Pnp transistor output extension module, 8 points (modbus)

Advertisement

COMPONENT IDENTIFICATION

Discrete Output Status Indicator LED
■ DISCRETE I/O STATUS INDICATOR LED
Discrete I/O modules including those for extensions have
LED indicators showing I/O signal status.
Contact ON
: LED ON
Contact OFF : LED OFF
■ OUTPUT TERMINAL ASSIGNMENT
6
7
8
+24 V
Y1
1
2
3
0 V
Y0
Y2
NO.
ID
FUNCTION
1
0V
0V
2
Y0
Output 0
3
Y2
Output 2
4
Y4
Output 4
5
Y6
Output 6
CONNECTING THE EXTENSION MODULE
1) Remove the extension connector cover located at the side
of the basic module.
2) Connect the extension module.
3) Mount the combined module on a DIN rail.
0
1
2
3
4
5
6
7
6
7
8
9
10
1
2
3
4
5
Output Terminals
9
10
Y3
Y5
Y7
4
5
Y4
Y6
NO.
ID
FUNCTION
6
+24V 24V DC (common)
7
Y1
Output 1
8
Y3
Output 3
9
Y5
Output 5
10
Y7
Output 7
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: + 81 ( 6 ) 6659-8201 Fax: + 81 ( 6 ) 6659-8510 E-mail: info@m-system.co.jp

CONNECTION DIAGRAM

Connect the unit as in the diagram below.
Output Connection Example
6
+24V
1
0V
2
Y0
10
Y7

WIRING INSTRUCTIONS

■ SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit. Applicable
wire size: 0.3 – 0.75 mm
2
3 (.12) max.
12 (.47) max.
R7M-EC8B
6
+24V
2
Y0
3
Y2
4
Y4
5
Y6
7
Y1
8
Y3
9
Y5
10
Y7
1
0V
+
4 min.
(.16)
3.2 (.13) dia.
EM-7803-P Rev.2