Compressor check
Measure the resistance value of each winding by using the tester.
Figure 63
Position
115V - 12K
Blue - Red
Blue - Black
2.13Ω
Red - Black
Table 46
36K Light
Position
Commercial
Cassette &
Ducted
Blue - Red
Blue - Black
0.65Ω
Red - Black
Table 47
Bosch Wall Mounted Ductless Split Air Conditioner / Heat Pump IDU-ODU - BTC 769102301 A (11.2022)
9K
12K
Regular
Regular
2.13Ω
2.13Ω
Resistance Value
48K Light
60K Light
Commercial
Commercial
Performance
0.37Ω
0.37Ω
1.82Ω
Figure 64
Resistance Value
18K
Regular
1.86Ω
9K
12K
18K
Max
Max
Max
Performance
Performance
1.82Ω
1.03Ω
24K
30K Light
Regular
Commercial
1.03Ω
0.75Ω
24K
36K
Max
Max
Performance
Performance
1.03Ω
0.10Ω
Service Manual
36K Light
Commercial
Wall Mounted
0.75Ω
48K
Max
Performance
0.10Ω