L2: DC bus high voltage protection
L2 protection
The power supply is abnormal
The DC bus voltage (P, N) is abnormal
Replace the inverter module
Note:
1.
The normal DC voltage between terminals P and N on inverter module should be 240-375V. When the voltage is higher than 500V, L2
protection will be appeared.
Yes
No
Yes
1
No
Figure 6-2.7: Inverter module terminals
U V W
Check the power supply
equipment
Replace the 3-phase bridge
rectifier
P
N
85