Trane TVR Pro CO Series Service Manual page 109

Hide thumbs Also See for TVR Pro CO Series:
Table of Contents

Advertisement

2.23 P9, H9: Fan module protection
Digital display output
Description
 Fan module protection.
 All units stop running.
 Error code is only displayed on the unit with the error.
Trigger / recover condition
 Trigger condition:
For P9 protection: Fan speed is too low.
For H9 protection: P9 protection appears ten times in 120 minutes.
 Recover condition: Fan speed go back to normal.
 Reset method:
For P9 protection: Resume automatically; For H9 protection: Manually restart.
Possible causes
 Switch ENC2 incorrectly set.
 Power or communication wires not connected properly.
 Fan motor blocked or has failed.
 Power supply abnormal.
 AC filter board damaged.
 Fan module damaged.
 Main PCB damaged.
Procedure
The capacity set on switch ENC2 on the
main PCB and the capacity given on the
unit's nameplate do not match
Some power wires or communication
wires of fan module are not connected
The fan motor is blocked or has failed
;
P9 / H9
No
properly
No
Ensure the setting on switch ENC2
matches the unit capacity given on the
unit's nameplate
Ensure power and communication wires
Yes
are connected properly
Remove obstruction or replace the fan
Yes
108
motor

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents