Nortek U-match Series Owner's Manual & Installation Instructions

Dc inverter, duct type unit

Advertisement

Quick Links

Nortek Global HVAC, LLC
Please read this owner's manual carefully before operation and retain it for future reference
Specifications & illustrations subject to change without notice or incurring obligations
If you have lost the owner's manual, please visit www.NortekHVAC.com for electronic version.
DC Inverter U-match Series
Duct Type Unit
Owner's Manual / Installation Instructions
Heat Pump
Indoor Unit
GDU18(5.3)USV4DH
GDU24(7.0)USV4DH
GDU30(8.8)USV4DH
GDU36(10.6)USV4DH
GDU42(12.3)USV4DH
GDU48(14.1)USV4DH
Outdoor Unit
GXH18(5.3)USV4DH
GXH24(7.0)USV4DH
GXH30(8.8)USV4DH
GXH36(10.6)USV4DH
GXH42(12.3)USV4DH
GXH48(14.1)USV4DH

Advertisement

Table of Contents
loading

Summary of Contents for Nortek U-match Series

  • Page 1 Nortek Global HVAC, LLC DC Inverter U-match Series Duct Type Unit Owner's Manual / Installation Instructions Heat Pump Indoor Unit Outdoor Unit GDU18(5.3)USV4DH GXH18(5.3)USV4DH GDU24(7.0)USV4DH GXH24(7.0)USV4DH GDU30(8.8)USV4DH GXH30(8.8)USV4DH GDU36(10.6)USV4DH GXH36(10.6)USV4DH GDU42(12.3)USV4DH GXH42(12.3)USV4DH GDU48(14.1)USV4DH GXH48(14.1)USV4DH Please read this owner’s manual carefully before operation and retain it for future reference Specifications &...
  • Page 2: Table Of Contents

    Contents 1 Safety Precautions ························································································ 1 2 Outline of the Unit and Main Parts ······························································ 2 3 Pre-Installation Check List ··········································································· 3 3.1 Standard Accessory Parts ········································································ 3 3.2 Selection of the Installation Location ·································································· 4 3.3 Pipe Connection Requirement ··········································································· 6 3.4 Electrical Requirement························································································...
  • Page 3: Safety Precautions

    DC Inverter U-match Series Duct Type Unit 1 Safety Precautions WARNING NOTICE: Failure to comply with warning notice could result in property damage, serious personal injury or death. CAUTION NOTICE: Failure to comply with caution notice could result in property damage or personal injury.
  • Page 4: Outline Of The Unit And Main Parts

    DC Inverter U-match Series Duct Type Unit 2 Outline of the Unit and Main Parts Fig. 2.1 Installer must properly connect refrigerant pipe, drain pipe, power cord, and ducworkt. The duct heater is arranged for use with rectangular duct.
  • Page 5: Pre-Installation Check List

    DC Inverter U-match Series Duct Type Unit 3 Pre-Installation Check List The standard accessory parts listed below are furnished and should be used as described. Table 3.1 Indoor Unit Accessories Name Appearance Q'ty Usage Wired Controller To control the indoor unit...
  • Page 6: Selection Of The Installation Location

    DC Inverter U-match Series Duct Type Unit Table 3.2 Outdoor Unit Accessories Name Appearance Q'ty Usage To plug the unused Drain Plug 1 or 3 drain hole To connect with the Drainage Connecter hard PVC drain pipe 3.2 Selection of the Installation Location Check the support structure to verify that it has sufficient load-carrying capacity to support the weight of the unit and it can be securely mounted..
  • Page 7 DC Inverter U-match Series Duct Type Unit (4). Install the unit where the drain pipe can be easily installed. (5). The more space that is open above the unit, the easier it will be to service. 3.2.2 Outdoor Unit Install the unit where it will not be tilted by more than 5°.
  • Page 8: Pipe Connection Requirement

    DC Inverter U-match Series Duct Type Unit 3.3 Pipe Connection Requirement The maximum length of the connection pipe is listed in the table below. Do not place the units where the distance exceeds the maximum length of the connection pipe.
  • Page 9: Electrical Requirement

    DC Inverter U-match Series Duct Type Unit 3.4 Electrical Requirement Electric Wire Size and Fuse Capacity. Table 3.4 Minimum Maximum Power Supply Fuse Capacity Circuit Overcurrent Indoor Units Ampacity Protection V/Ph/Hz 208/230V ~ 60Hz GDU18(5.3)USV4DH 208/230V ~ 60Hz GDU24(7.0)USV4DH 208/230V ~ 60Hz GDU30(8.8)USV4DH...
  • Page 10: Installation Of The Unit

    DC Inverter U-match Series Duct Type Unit between the wired controller and the indoor unit, with their longest lengths of 30m (98-1/2 feet). Please select the appropriate line length per the actual installation conditions. The communication lines cannot be twisted together.
  • Page 11 DC Inverter U-match Series Duct Type Unit For the units: GDU24(7.0)USV4DH ~ GDU42(12.3)USV4DH For the units: GDU48(14.1)USV4DH Fig. 4.1 Table 4.1 Unit: mm (inch) Item Model 1035 GDU18(5.3)USV4DH (37-1/4) (24-3/8) (29) (35-1/8) (40-7/8) (28-3/8) (29) (4-7/8) (10-1/2) GDU24(7.0)USV4DH 1100 1160...
  • Page 12 DC Inverter U-match Series Duct Type Unit 4.1.2 Drilling Holes for Bolts and Installing the Bolts Using the installation template, drill holes for bolts (four holes) (Fig. 4.2). 4.1.3 Installing the Suspension Bolts (1). Install the bolts to the ceiling at a place strong enough to hang the unit. Mark the bolt positions from the installation template.
  • Page 13: Installation Of The Outdoor Unit

    DC Inverter U-match Series Duct Type Unit 4.1.4 Leveling The water level test must be done after installing the indoor unit to make sure the unit is level, as shown below. Fig. 4.7 4.2 Installation of the Outdoor Unit Install the unit where it will not be tilted by more than 5°.
  • Page 14: Installation Of The Connection Pipe

    DC Inverter U-match Series Duct Type Unit 4.2.2 Condensate Drainage of the Outdoor Unit (for the heat pump unit only) (Fig. 4.9) (1). It is required to install a drain pipe for the outdoor unit to drain condensate water during heating operation (only for the heat pump unit).
  • Page 15 DC Inverter U-match Series Duct Type Unit Fig. 4.11 (2). Do not bend the pipes in an angle more than 90°. (3). When pipes are repeatedly bent or stretched, the material will weaken making it more likely to break. Do not bend or stretch the pipes more than three times.
  • Page 16 DC Inverter U-match Series Duct Type Unit When the flare nut is tightened properly by your hand, use a torque wrench to finish tightening it. Fig. 4.13 Fig. 4.14 Table 4.3 Flare nut tightening torque Pipe Diameter Tightening Torque 6mm (1/4inch) 15~30N·m (11~22ft.-lb.)
  • Page 17 DC Inverter U-match Series Duct Type Unit 4.3.5 Checking the Pipe Connections for Gas Leaks For both indoor and outdoor unit, be sure to check the joints for gas leaks with a gas leakage detector. 4.3.6 Heat Insulation on the Pipe Joints (Indoor Side Only) Attach coupler heat insulation (large and small) to the pipe connections.
  • Page 18: Vacuum And Gas Leakage Inspection

    DC Inverter U-match Series Duct Type Unit (2). If the outdoor unit is installed higher than the indoor unit (See Fig. 4.18) 1). Wrap tape from the lower end working up.. 2). All pipes must be bound and taped together.
  • Page 19 DC Inverter U-match Series Duct Type Unit (7). Slightly open the liquid valve and let some refrigerant into the connection pipe to balance the pressure inside and outside of the connection pipe, so that air will not come into the connection pipe when removing the hose. Note that the gas and liquid valve can be opened fully only after the manifold valve assembly is removed.
  • Page 20: Installation Of The Drain Hose

    DC Inverter U-match Series Duct Type Unit When height difference between the indoor unit and outdoor unit is more than 10m (33 feet), an oil bend should be employed for every 6m (20 feet). Fig. 4.20 4.5 Installation of the Drain Hose 4.5.1 Installation of Drain Piping...
  • Page 21 DC Inverter U-match Series Duct Type Unit 1~1.5m (3-5 feet) Fig. 4.22 Fig. 4.23 Fig. 4.24...
  • Page 22 DC Inverter U-match Series Duct Type Unit (5). Use a suitable drain hose, and see Table 3.3 for size. (6). There is a drain port on both the left and right sides. Select the drain port to match your installation (Fig. 4.23).
  • Page 23 DC Inverter U-match Series Duct Type Unit drain ports also need to be insulated properly as described above. 4). The drain hose for the unit with the condensate pump should be arranged as shown in the figure below. Fig. 4.28 The vertical height of the drain hose should be 75mm (3inch) or less to reduce unnecessary pressure on drain pump.
  • Page 24 DC Inverter U-match Series Duct Type Unit 4.5.2 Testing of Drain Piping After piping work is finished, check if drainage flows smoothly. As shown in the figure, add approximately 1 liter/quart of water slowly into the drain pan and check drainage flow during COOL running.
  • Page 25: Installation Of The Duct

    DC Inverter U-match Series Duct Type Unit 4.6 Installation of the Duct 4.6.1 Dimensions of the Supply Air Outlet/Return Air Inlet Fig. 4.32 Supply Air Outlet Fig. 4.33 Return Air Inlet Table 4.5 Unit: mm (inch) Supply Air Outlet Return Air Inlet...
  • Page 26 DC Inverter U-match Series Duct Type Unit 4.6.2 Installation of the Supply Air Duct (1). Installation of the Rectangular Duct. Table 4.6 Installation of the rectangular duct Name Name Hanger Filter Main Air Air Intake Supply Pipe Pipe Canvas Air Supply...
  • Page 27: Electrical Wiring

    DC Inverter U-match Series Duct Type Unit connect the return air louver. For convenience, to adjust the height of the return air outlet, a cutting of canvas duct can be used. (5). More noise is likely to be produced in the bottom return air mode than the back return air mode, so it is suggested to install a silencer and a static pressure box to minimize the noise.
  • Page 28 DC Inverter U-match Series Duct Type Unit Perform wiring work in accordance with standards so that the air conditioner can be operated safely. Install a dedicated circuit breaker in accordance with the related laws and regulations and standards. The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances.
  • Page 29 DC Inverter U-match Series Duct Type Unit Fig. 4.38 Fig. 4.39 (3). How to fix connection cord and power cord with cord clamp After passing the connection cord and power cord through the insulation tube, fasten it with the cord clamp (Fig. 4.39).
  • Page 30 DC Inverter U-match Series Duct Type Unit Single-phase units (36k-48k) Fig. 4.40 (5). Electric wiring of indoor unit side Remove the electric box cover from the electric box sub-assy and then connect the wire. Fig. 4.41 The F, C, O connect to the COMMOM, CLOSE and OPEN terminal of the fresh air valve respectively.
  • Page 31: Installation Of Controllers

    DC Inverter U-match Series Duct Type Unit The high-voltage and low-voltage lines should be fixed separately and securely, with internal big clamps for the former and small clamps for the latter. Tighten the indoor/outdoor connection cord and power cord respectively on the terminal boards with screws.
  • Page 32: Testing

    DC Inverter U-match Series Duct Type Unit 6 Testing 6.1 Trial Operation and Testing (1). The meaning of error codes as shown below: Table 6.1 Number Error code Error Remarks Compressor high pressure protection Indoor anti-freeze protection Compressor low pressure protection, refrigerant...
  • Page 33 DC Inverter U-match Series Duct Type Unit Drive reset protection Over-current protection Communication error between main control and drive Drive module sensor error Drive module over temperature protection Zero passage protection AC current protection Drive current error Sensor connecting protection...
  • Page 34: Working Temperature Range

    DC Inverter U-match Series Duct Type Unit 6.2 Working Temperature Range Table 6.2 Indoor Side Outdoor Side Test Condition DB(°C/ WB(°C/ ) DB(°C/ WB(°C/ ) Nominal Cooling 26.7(80.0) 19.4(67.0) 35.0(95.0) 23.9(75.0) Nominal Heating 21.1(70.0) 15.6(60.0) 8.33(47.0) 6.11(43.0) Rated Cooling 26.7(80.0) 19.4(67.0)
  • Page 35: Unit Function

    DC Inverter U-match Series Duct Type Unit 7 Unit Function 7.1 Setting Double Indoor Room Sensors This series of ducted air-conditioning unit has two indoor room sensors. One is located at the air intake of the indoor unit and the other one is located inside the wired controller.
  • Page 36: Fresh Air Control

    DC Inverter U-match Series Duct Type Unit 7.3 Fresh Air Control Fresh air controls regulate the amount of fresh air brought in from outside. The function helps to create a healthier environment by improving the indoor air quality (IAQ). It can also help to regulate electricity usage by the controlling the amount of outside air used.
  • Page 37: Routine Maintenance

    DC Inverter U-match Series Duct Type Unit The air filter is dirty or blocked. There is heat source or too many people inside the room. The door or window is open. Poor cooling effect. There is obstacle at the air intake or outlet.
  • Page 38 DC Inverter U-match Series Duct Type Unit cool water. Do not use detergent or hot water to avoid filter shrinking or deforming. After cleaning dry them in the shade. 18k: 24k~48k: (3). Replace the air filter.
  • Page 40 Specifications & illustrations subject to change without notice or incurring obligations. O’Fallon, MO (08/16) © Nortek Global HVAC, LLC 2016. All Rights Reserved. 543E-0816...