MB-LI-4 Hi
Pulse counter,
4-channel,
with Modbus RTU output
Do not dispose of this device in the trash along with other waste! According
to the Law on Waste, electro coming from households free of chage and
can give any amount to up to that end point of collec� on, as well as to sto-
re the occasion of the purchase of new equipment (in accordance with the
principle of old-for-new, regardless of brand). Electro thrown in the trash or
abandoned in nature, pose a threat to the environment and human health.
Purpose
The MB-LI-4 pulse counter is used for counting the AC/DC signals
generated by external devices to determine the number of com-
pleted work cycles and for exchanging the data via RS-485 port
in accordance with the Modbus RTU protocol.
Functions
» 4 independent counters;
» Counter input designed to work with AC/DC signals 160÷265 V;
» Factor adjustment (a floating-point value);
» Rescaled value (Number of pulses × factor);
» Selecting a mode of state 1 trigger: high or low voltage;
» Selecting an input pulse edge (leading or trailing);
» Frequency filter that allows you to limit the maximum frequ-
ency of counted pulses (to eliminate interferences on the
input of the counter);
» Memory of counter status after power failure;
» Digital input.
F&F Filipowski sp. j.
Konstantynowska 79/81, 95-200 Pabianice, POLAND
phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71
www.fif.com.pl; e-mail: biuro@fif.com.pl
- 1 -

Advertisement

Table of Contents
loading

Summary of Contents for F&F MB-LI-4 Hi

  • Page 1 F&F Filipowski sp. j. Konstantynowska 79/81, 95-200 Pabianice, POLAND phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71 www.fif.com.pl; e-mail: biuro@fif.com.pl MB-LI-4 Hi Pulse counter, 4-channel, with Modbus RTU output Do not dispose of this device in the trash along with other waste! According to the Law on Waste, electro coming from households free of chage and can give any amount to up to that end point of collec�...
  • Page 2 Functioning The MB-LI-4 module is a four-channel one-way counter. Each channel is independent and counts the impulses in accordance with individual settings. The results are presented in the form of a Number of pulses and rescaled value in a range from 0 to ~4,29 billion. Reading of the counter can be reset independently for each channel.
  • Page 3 Mounting The use of anti-interference and surge filters (such as OP-230) is recommended. It is recommended to use shielded twisted-pair cables to connect the module to another device. When using shielded cables, ground the screens only on one side and as close to the device as possible. Do not route signal cables in parallel in close proximity to high and medium voltage lines.
  • Page 4: Wiring Diagram

    1. Before installing the module, set the selected Modbus com- munication parameters and measurement options. 2. Disconnect the power supply in distribution box. 3. Install the module on the rail. 4. Connect the module power supply to terminals 1-3 as indica- ted.
  • Page 5: Terminal Description

    Terminal description 9÷30 V DC power supply RS-485 serial port IN1 counter input IN2 counter input COM input (common) for IN1 and IN2 IN3 counter input IN4 counter input COM input (common) for IN3 and IN4 - 5 -...
  • Page 6 Communication settings reset A configuration jumper is available under the module casing. Starting the controller with the jumper closed restores the facto- ry settings of the communication parameters. To do this, remove the casing of the module and put the jumper on both pins. After the reset is done, remove the jumper.
  • Page 7: Communication Parameters

    Security 1. Galvanic isolation between the IN..., COM... contacts and the rest of the circuit (min. 2.5 kV). and the rest of the system (min. 2.5 kV). 2. No galvanic isolation between module power supply and RS- 485 lines. 3. Overcurrent protection for power supply and communication inputs (up to a maximum of 60 V DC) with automatic return function.
  • Page 8: Communication Registers

    Communication parameters cont. Network address range 1÷245 (1) (factory settings) 1: Read inputs status (0×01 – Read Coils) 3: Read the values of a group of registers Command codes (0×03 – Read Holding Register) 6: Set the value of a single register (0×06) –...
  • Page 9 Communication registers cont. address description func. type atr. Read current and write new number of stop bits: 0:1 bit/1:1,5 bita/2:2 bity Restore the factory settings: Set the value 1. Note! Changes in communication parameters (baud rate, number of stop bits, parity) are only taken into account only after the power is restarted.
  • Page 10 Digital input registers address description func. type atr. Read inputs status: 0/1 – 4 bits (e.g. 1001) Order: | In4 | In3 | In2 | In1 | In1: Input status 0/1 In2: Input status 0/1 In3: Input status 0/1 In4: Input status 0/1 Counters registers address description...
  • Page 11 Counters registers cont. address description func. type atr. In4: Number of pulses 65÷66 R66×256²+R65 19÷20 In1: Scaled value float In1: Scaled value – 21÷22 integer part In1: Scaled value – 23÷24 fractional part: 6 digits ×0.000001 (250000 -> 0.25) In1: Counter reset. Enter value 0.
  • Page 12 Counters registers cont. address description func. type atr. 51÷52 In3: Scaled value float In3: Scaled value – 53÷54 integer part In3: Scaled value – 55÷56 fractional part: 6 digits ×0.000001 (250000 -> 0.25) In3: Counter reset. Enter value 0. 67÷68 In4: Scaled value float In4: Scaled value –...
  • Page 13: Configuration Registers

    Configuration registers address description func. type atr. In1: Multipier. Range 1÷10000. In1: Divisor. Range 1÷10000. In2: Pulse time minimum [ms]. Range 1÷15000. In2: Logic. 0: Falling slope 1: Rising slope In2: Multipier. Range 1÷10000. In2: Divisor. Range 1÷10000. In3: Pulse time minimum [ms]. Range 1÷15000.
  • Page 14 Configuration registers cont. address description func. type atr. In3: Divisor. Range 1÷10000. In4: Pulse time minimum [ms]. Range 1÷15000. In4: Logic. 0: Falling slope 1: Rising slope In4: Multiplier. Range 1÷10000. In4: Divisor. Range 1÷10000. The ratio setting for the scaled value is the result of multiplying and divi- ding the set values of the registers (e.g.
  • Page 15 Technical data power supply 9÷30 V DC number of counting inputs counting input voltage 160÷265 V AC/DC maximum counting frequency 100 Hz maximum number of pulses (4.294.967.295) input circuit impedance ≥10 kΩ port RS-485 communication protocol Modbus RTU operating mode Slave power indication green LED...
  • Page 16: Warranty

    Warranty The F&F products are covered by a warranty of the 24 months from the date of purchase. Effective only with proof of purchase. Contact your dealer or directly with us. CE declaration F&F Filipowski sp. j. declares that the device is in conformity with the essential requirements of The Low Voltage Directive (LVD) 2014/35/EU and the Electromagnetic Compatibility (EMC) Directive 2014/30/UE.