F&F MB-LI-4 Hi Manual page 11

Pulse counter, 4-channel, with modbus rtu output
Table of Contents

Advertisement

address
In4: Number of pulses
65÷66
R66×256²+R65
...
...
19÷20
In1: Scaled value
In1: Scaled value –
21÷22
integer part
In1: Scaled value –
23÷24
fractional part: 6 digits
×0.000001 (250000 -> 0.25)
In1: Counter reset.
31
Enter value 0.
35÷36
In2: Scaled value
In2: Scaled value –
37÷38
integer part
In2: Scaled value –
39÷40
fractional part: 6 digits
×0.000001 (250000 -> 0.25)
In2: Counter reset.
47
Enter value 0.
Counters registers cont.
description
- 11 -
func.
type
03
int
...
...
03
float
03
int
03
int
06
int
03
float
03
int
03
int
06
int
atr.
R
...
R
R
R
W
R
R
R
W