16.1 Internal Faults
Internal faults are the faults, which do not need any external signals and are detected by the system
itself. They are:
Generator Fails to Start.
Generator Voltage Unhealthy
Generator Frequency Unhealthy.
Generator over Speed.
Generator Fails to Stop.
Over Load
16.2 External Faults
Those faults which cannot be sensed by the unit itself (these faults are not reflected by the generator
voltage) and are to be provided externally. They are:
LLOP
HWT
RWL
Fuel
Emergency
V-Belt
16.3 Fault Reset
Internal Faults & LLOP fault:
All internal faults and LLOP fault can be reset by pressing (R) switch after the generator is
stopped.
External Fault except LLOP & V-Belt faults:
These faults cannot be reset till the engine is running and/or fault conditions persist. Once the
faults are rectified, the fault can be reset by pressing Reset switch (R). In case the engine fails
to stop "STOP KEY" can be pressed for manual attempt to stop engine
16.0
Communication
RS232
USB
Modbus on Rs485 (optional)
Model Selection
17.0
ECON-M
: Manual Controller with no AMF function.
ECON-A
: AMF Controller with built-in Manual Mode.
18.0
Terminal Numbers
Terminal No.
1
2
3
4
5
6
7
8
Cat_ECON-06-15 -Ver1.0.
Description
NC
NC
NC
CT Common
CT B
CT Y
CT R
NC
Page 19/21