Fujitsu UTY-VMSX Installation Manual page 7

Modbus convertor for indoor unit
Table of Contents

Advertisement

DIP Switch Setting
MODBUS
convertor
address
SET5-1 SET5-2 SET5-3 SET5-4 SET4-1 SET4-2 SET4-3 SET4-4
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
ON:
/ OFF:
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
(2) MODBUS communication setting: Baud rate setting (SET6-4)
ON: 19200bps
OFF: 9600bps (Default)
(3) MODBUS communication setting: Parity setting (SET6-3)
ON: odd
OFF: even (Default)
* When the STOP bit setting is "2bit," parity is set to "None" regardless
of the setting of this switch.
(4) MODBUS communication setting: Stop bit setting (SET6-2)
Stop bit can be set (1 bit or 2 bit).
ON: 2bit
OFF: 1bit (Default)
(5) MODBUS communication setting: MODBUS communication terminal
resistance (SET7-4)
MODBUS communication terminal resistance can be set (Valid or
invalid).
Terminal resistance: 120Ω
Set the terminal resistances as necessary.
For MODBUS system, terminal resistances are necessary at the both
ends of communication line. (Total 2 terminal resistances)
Set the terminal resistances at the both ends to be valid and set the
terminal resistances other than at the both ends to be invalid.
ON: Terminal resistance valid
OFF: Terminal resistance invalid (Default)
* The switches from (1) to (4) are read at the time of power-on. Even if
these switches are changed after power-on, the setting is not refl ected.
(6) Unused SW
SET6-1, SET7-1 to 3: Not used
All Default settings: "OFF"
(: Factory setting)