blinking green until it turns to solid white. If it's already Internet connected,
the indicator will turn to solid green.
Status indicator shall be solid green.
(4)
Load indicator shall be solid green and all appliances connected to Load shall
(5)
be live.
CAUTION: If the Load indicator is not solid green, please stop the operation,
otherwise the device may be damaged. Please turn off the power to check
whether the battery wiring sequence is correct, and whether the battery
and voltage are normal. Please restart the operation after the exception is
cleared.
Run indicator shall blink in yellow alarming PV disconnection
(6)
CAUTION: DO NOT switch on PV switch until step 12.
Switch circuit breaker on from MAIN service panel (to connect iCAN NetZero
(7)
Plus to the grid), switch on Grid Switch on Universal PCS and wait for the GRID
indicator to go solid green.
Wait approximately 5 minutes until the device is grid tied.
(8)
(ONLY applicable in the 1st boot testing of iCAN NetZero Plus) Cut off the grid
(9)
to see if house rolls back to battery. ( Some loads might be interrupted.
Operation on the circuit breaker may trigger overcurrent protection, thus
blocking Universal PCS from energizing LOAD for 30 seconds.)
(ONLY applicable in the 1st boot testing of iCAN NetZero Plus) If power rolls
(10)
back to battery and house is energized, everything is working as expected.
(ONLY applicable in the 1st boot testing of iCAN NetZero Plus)
(11)
Turn Grid back on (Switch circuit breaker ON from MAIN service panel to
connect iCAN NetZero Plus to the grid); switch on GRID SWITCH on Universal
PCS, and wait until the GRID indicator goes solid green.
Switch on PV SWITCH on Universal PCS. PV should start producing energy
(12)
roughly in 10 ~ 20 seconds.
If everything works as expected, the system should function normally now.
(13)
NOTE: When the system has been started and proper operation has been
verified, put the door of the battery system back on the cabinet and fix the door.
NOTE: Watch the ALARM on the APP all the time.