The generator may not work
properly.
Remote control cable is
disconnected.
The Status Indicator on BCMS module/battery system is solid red and the
(6)
Status Indicator on at least one battery module is solid red.
The battery system is in the
most critical level protection
mode.
The Status Indicator on BCMS module/battery system is solid red and the
(7)
Status Indicator on every battery module is solid green.
Battery system over-current/
short circuit protection.
The Status Indicator on BCMS module/battery system is solid red and the
(8)
Status Indicator on at least one battery module is solid yellow or off.
The battery system is in the
low voltage protection mode.
The battery system is in the
High voltage protection mode.
The Status Indicator on BCMS module/battery system keeps blinking in
(9)
blue for over 60 seconds.
Battery system failed in self-
inspection.
The Status Indicator on at least one battery module keeps blinking in
(10)
blue for over 30 seconds.
Check the generator.
Check and reconnect the cable.
Charge the battery, or reboot the battery
system. If it does not recover, shut it down
and contact us.
Disconnect output switch of battery
system, check if there is an external short
circuit, and reboot the battery system. If it
does not recover, shut it down and
contact us.
Charge the battery.
Check if the communication cable for
BCMS and EMS is disconnected;
Leave it switched ON for 30 minutes.
If it does not recover, shut it down and
contact us.
Reboot the battery system.