E: 11. Serial Communication Error (Serial Forward Transfer Error) (Indoor Unit) - Fujitsu ABYG18KRTA Service Manual

Ceiling type air conditioner
Hide thumbs Also See for ABYG18KRTA:
Table of Contents

Advertisement

2-2. E: 11. Serial communication error (Serial forward transfer
error) (Indoor unit)
Wired remote
Indicator
controller
Detective actuator
Indoor unit
Forecast of cause
Check point 1. Reset the power and operate
Does error indication show again?
→ If no, go to
"Check point
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
→ If there is an abnormal condition, correct it by referring to the installation manual or the "DESIGN
& TECHNICAL MANUAL".
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 198 V (AC 220 V -10%) to AC 264 V (AC 240 V +10%) appears at
outdoor unit terminal L - N.

2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)

Error code
When the outdoor unit cannot receive the serial signal
Main PCB
from indoor unit more than 10 seconds.
1-2".
- (03-5) -
E: 11
Connection failure
External cause
Main PCB failure
+
-
2. Troubleshooting with error code

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents