Bci-I Controller Module - Physical Specifications; Backward Compatibility - Trane BACnet BCI-I Installation Manual

Table of Contents

Advertisement

BCI-I Controller Module — Physical Specifications
Dimensions
Height: 4.00 inches (101.6 mm)
Width: 5.65 inches (143.6 mm)
Depth: 2.17 inches (55 mm)
Operating environment
-40° to 70°C (-40° to 158°F)
5% to 95% relative humidity non-condensing
Storage environment
-44°C to 95°C (-48°F to 203°F)
5% to 95% relative humidity non-condensing
UL Approval
UL unlisted component
BACnet Testing Laboratory (BTL®) certification.
Per ANSI/ASHRAE Standard 135-2004. For more details, refer to the BTL website at
www.bacnetassociation.org.
Power requirements
19 to 30VAC (24VAC nominal)
Maximum VA = 12VA
50 or 60 HZ
Tools Required
1 Philips head screwdriver
1 Flathead screwdriver

Backward Compatibility

IntelliPak I units with design sequence "F" (20-75 ton) or "6" (90-130 ton) (February 2009) or greater
are shipped with the correct software versions (design sequence is the 10th digit of the unit model
number). Units with lower design sequences will report "COMM 5" instead of "BACNET" on the
BAS Communications Software Revision Number screen. Also, for IntelliPak units with design
sequences prior to "5" (20-75ton) or "X" (90-130 ton), module change(s) are required (this is for units
built before May 2003).
IntelliPak II units with design sequence "D0" (90-150 ton) AND HI software version 35.06 or greater
are shipped with the correct software versions (design sequence is the 10th and 11th digits of the
unit model number). Units with lower design sequences or earlier HI software version will report
"COMM 5" instead of "BACNET" on the BAS Communications Software Revision Number screen.
To verify software versions, press the CONFIGURATION button on the human interface, then press
the NEXT button until the software revision screens are displayed.