DRY OPERATION
Vane
setting notch
w 8 ~ 9 Refer to page 31.
w 12
When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
w 13
Compressor ON time is decided by room temperature. Refer to page 32.
w 14
In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
DRY
operation
Four-way valve / OFF
NO
Initial dry
operation
YES
Vane initial setting
YES
Room temperature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
NO
Compressor &
thermostat ON
YES
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
w 8
w 12
NO
NO
w 9
YES
NO
W 14
33
YES
3-minute
time delay
NO
w 9
Compressor &
thermostat
ON
NO
10-minute
NO
compressor
OFF
YES
w 13
Compressor ON
time set
Compressor ON
W 14
Fan speed LOW