[2] Installation Space Requirements

<1> Single unit installation
Secure enough space around the unit as shown in the figures below.
(1) Walls around the unit do not exceed the height limit.
80
80
A
(2) There is a wall above the unit.
Min. 45º
(3) One or more of the walls around the unit are taller than the maximum allowable height <h>.
80
h
80
A
A Walls are lower than the unit's height.
Max. 500
A
300
Min. 500
Min. 240
Flow hood
300
(field supplied)
h
80
Max. 500
A
300
Min. 500 + h
A Walls are lower than the unit's height.
Min. 1000
h
Max. 500
A
300 + h
80
A
Min. 500 + h
8
h
80
h
A
80
A
Min. 500 + h
<Unit: mm>
h
Max. 500
300 + h

Advertisement