Do not unnecessarily change the switch settings or
touch other parts in the refrigerant circuit.
Doing so may change the operation mode or damage the
unit.
To reduce the risk of malfunctions, use the unit within its
operating range.
Do not switch on or off the main power in a cycle of
shorter than 10 minutes.
Short-cycling the compressor may damage the compressor.
To maintain optimum performance and reduce the risk of
malfunction, keep the air pathway clear.
To ensure proper operation of the unit, periodically
check for proper concentration of anti-freeze.
Inadequate concentration of anti-freeze may compromise the
performance of the unit or cause the unit to abnormally stop.
Take appropriate measures against electrical noise
interference when installing the air conditioners in
hospitals or facilities with radio communication
capabilities.
Inverter, high-frequency medical, or wireless communication
equipment as well as power generators may cause the air
conditioning system to malfunction. Air conditioning system
may also adversely affect the operation of these types of
equipment by creating electrical noise.
Check the water system, using a relevant manual as a
reference.
Using the system that does not meet the standards (including
water quality and water flow rate) may cause the water pipes
to corrode.
To reduce the risk of power capacity shortage, always use a
dedicated power supply circuit.
To reduce the risk of both the breaker on the product side
and the upstream breaker from tripping and causing
problems, split the power supply system or provide protection
coordination between the earth leakage breaker and no-fuse
breaker.
When servicing the refrigerant, open and close the check
joint using two spanners, as there is the risk of
refrigerant leaking due to damaged piping.
Please build the water circuit so that it is a closed
system.
Do not use water directly for showers or other applications.
Do not allow other heat source water to mix with the water
circuit.
Store the unit in a room large enough to allow clearance
in the event of refrigerant leakage.
Refrigerant R454C is flammable. Do not use a naked-
flame type detector.