(3) Combination of face-to-face and side-by-side installations
• There are walls in the back and the front of a given
group of units.
*
h
500
(4) Water pipe installation
Pattern A
Wall
Front
Front
Wall
A
Min. 160
A
<Top view>
If the product width (labeled A in the figure) times
the number of units that are installed side by side
exceeds 6 m, leave a space of 1000 mm
between each block. Each block is defined as a
group of units that fit within 6 m.
Min. 300 + h
Min. 900
*
Min. 300 + h
Water pipe
Front
Water pipe
Min. 160
<Side view>
• There is a wall on one side and either the front or
the back of a given group of unit.
h
500
Min. 1000 + h
Pattern B
Min. 500
B Min. 500
Wall
Wall
Water pipe
If the product depth (labeled B in the figure) times the
number of units that are installed in rows exceeds 6 m,
leave a space of 1000 mm between each block. Each
block is defined as a group of units that fit within 6 m.
10
h
Unit height
*
Min. 500
Min. 500
Min. 300
<Top view>
h
500
Min.
300 + h
*
Min. 900
Front
Wall
Wall
<Side view>