Installing user interfaces
1.
Follow device Installation Instructions to select appropriate physical placement of user interfaces.
2.
Take care not to damage the wall surface surrounding user interfaces particularly when they have the
light wash feature (PDTS, PAxBP, PADP and PATP).
3.
All devices must be level and mounted consistently (vertically or horizontally) using the screws provided.
A wall box may be required to comply with local electrical standards. The mounting plate must sit flat
onto the wall surface.
4.
Wall box screw holes must be horizontal when mounting Revolution user interfaces.
5.
Where panels and buttons are engraved, check all labels are in the correct position before clipping into
position.
6.
Do not remove buttons from their protective/alignment sheet until the project is handed over.
7.
User Interface sensor holes must be positioned at the bottom of the device. Devices have arrows to show
correct orientation. If mounting Touchscreen in portrait mode Ethernet port must face downwards.
8.
User Interface panels should have 30 cm (12 in) clearance from any metal objects or nearby cables
(mains and data). Unearthed nearby metal objects such as stud work and door frames, may lead to false
triggering of the lightwash effect. Ensure wall box and mounting plate are earthed according to the
supplied installation instructions.
9.
For all user interfaces, the cable should exit towards the bottom of the panel to avoid moisture ingress.
10. Touchscreens require an external power supply.