Controller Terminals - Honeywell Centra Line MERLIN NX Series Installation Instructions Manual

Ip and ms/tp vav controller
Hide thumbs Also See for Centra Line MERLIN NX Series:
Table of Contents

Advertisement

Controller Terminals

Type
Legend
Printing
1
2
V0
Power
3
~
4
AC OUT
5
SR IN
6
SR1
7
C
8
SR2
9
SR3
SSR
10
C
11
SR4
12
SR5
13
C
14
WM1
SYLK
15
WM2
16
+
RS
17
-
485
18
COM
19
IO1
20
C
21
IO2
22
IO3
23
C
UIO
24
IO4
25
IO5
26
C
27
IO6
28
C
29
IO7
30
C
20 VDC
20 VDC
31
OUT
(a
+
32
BACnet
(a
-
33
MS/TP
(a
COM
34
(a
Terminal 32,33, and 34 are available in MSTP variant only.
(b
Terminal for IP variant only.
MERLIN NX IP AND MST/TP VAV CONTROLLER - INSTALLATION INSTRUCTIONS
Earth Ground (Connected to power earth ground)
Ground
Power supply voltage (Connected to 24VAC~)
24VAC~ output
SSR POWER input (Connected to terminal 4 (AC OUT) by a jumper wire)
SSR1 output (if SSR1 is on this pin should be 24VAC~)
Ground
SSR2 output (if SSR2 is on this pin should be 24VAC~)
SSR3 output (if SSR3 is on this pin should be 24VAC~)
Ground
SSR4 output (if SSR4 is on this pin should be 24VAC~)
SSR5 output (if SSR5 is on this pin should be 24VAC~)
Ground
Interface for Sylk™ bus
Interface for Sylk™ bus
RS 485 Modbus interface
RS 485 Modbus interface
Ground
Universal signal input/output1 (Input<"0-20mA" "0-10V" "NTC10K" NTC20K" "RTD" >; Output<"0-
10V" "0-20mA">
Ground
Universal signal input/output2 (Input<"0-20mA" "0-10V" "NTC10K" NTC20K" "RTD" >; Output<"0-
10V" "0-20mA">
Universal signal input/output3 (Input<"0-20mA" "0-10V" "NTC10K" NTC20K" "RTD" >; Output<"0-
10V" "0-20mA">
Ground
Universal signal input/output4 (Input<"0-20mA" "0-10V" "NTC10K" NTC20K" "RTD" >; Output<"0-
10V" "0-20mA">
Universal signal input/output5 (Input<"0-20mA" "0-10V" "NTC10K" NTC20K" "RTD" >; Output<"0-
10V" "0-20mA">
Ground (Connected to 24VAC~ground)/System ground
Universal signal input/output6 (Input<"0-20mA" "0-10V" "NTC10K" NTC20K" "RTD" >; Output<"0-
10V" "0-20mA">
Ground
Universal signal input/output7 (Input<"0-20mA" "0-10V" "NTC10K" NTC20K" "RTD" >; Output<"0-
10V" "0-20mA">
Ground
20VDC power output
Signal for RS 485 bus +
Signal for RS 485 bus -
Ground
IP ethernet RJ45-1/RJ45-2
Description
(b
7
EN1Z-1076GE51 R0722

Advertisement

Table of Contents
loading

Table of Contents