Introduction
1

General Information

1.1
All FirePro Fire Extinguishing Aerosol Generators use the latest generation FPC solid compound.
Upon activation, the solid compound is transformed into a rapidly expanding, highly efficient
gas, based on Potassium salts.
Generators have a certified life of 15 years, with minimal maintenance required.
Ozone Depletion Potential (O.D.P.) = 0
Global Warming Potential (G.W.P.) = 0

Self Activation Temperature

1.2
FirePro Condensed Aerosols have a built-in fail-safe activation system ensures operation of the
generators when required, even if everything else fails.
When the temperature of the Aerosol units reaches 300°C the unit will activate
DO NOT Carry out any welding or grinding work in the vicinity of the aerosol units.
Handling and Storage - when handling the Condensed Aerosol Generators do not:
1.3
Disassemble the unit
Carry out any welding or grinding work in the
vicinity
of
components.
STORAGE and OPERATIONAL CONDITIONS
Temperature: –54 and +54°C
Service life: 15 years (date of manufacture appears on each generator)
Page | 1
It does not deplete oxygen levels.
the
fire
extinguishing
Fire Control Panel - Model 08451
Atmospheric Life Time (A.L.T.) = 0
Non-corrosive & Non-toxic
Exert force or impact which creates
physical or mechanical damage to the
system
casing.
Humidity: maximum 98% RH
SYSTEM ISOLATION
The FirePro Aerosol
Rev 1.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 08451 and is the answer not in the manual?

Questions and answers

Summary of Contents for FirePro 08451

  • Page 1 Rev 1.0 Introduction General Information All FirePro Fire Extinguishing Aerosol Generators use the latest generation FPC solid compound. Upon activation, the solid compound is transformed into a rapidly expanding, highly efficient gas, based on Potassium salts. It does not deplete oxygen levels.
  • Page 2 Fire Control Panel - Model 08451 SYSTEM ISOLATION Rev 1.0 Isolation using the Control Panel Isolate Function Normal Condition Panel Isolated To isolate the control panel, press and hold Single Button until a 1 beep and the “Isolated” LED is illuminated.
  • Page 3 Rev 1.0 Isolation by Unplugging the FirePro Units All FirePro Aerosol Generators are fitted with a Deutsch Plug. Unplugging the unit it will remove it from the System. Ensure that all units are unplugged in the system as remaining units may be operational.

Table of Contents