Power Distribution Frame Upgrades; Office Alarm System Features - Nortel DMS-100 Series Reference Manual

Alarm system description
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

4-10 Version 2 Enhanced Alarm System
allows the addition of up to ten additional exit alarm panels to the alarm
system.
The extension circuit permits selective control of the audible alarm panels.
You require control when audible alarm panels are configured with the
audible alarm cutoff control circuit (NT5X86AA) and the audible alarm
cutoff key panel (NT5X86AB). The audible alarm cutoff key panel is
located at the MAP terminal. The audible alarm cutoff key panel allows you
to selectively disable the two main audible alarm panels and the four
extended audible alarm panels. Figure 4-6 shows the audible alarm cutoff
key panel.
When you extend audible alarm capability, a ringing generator must be
available for the extension circuit.
Figure 4-6
Audible alarm cutoff key panel
Alarm Off

Power distribution frame upgrades

To upgrade the FSP in a PDC to support the EAS function, you use the
NT0X42XC conversion kit. This kit includes an NTFX05AA card to detect
outages on the A or B power feeds at the PDC.

Office Alarm System features

Table 4-2 list the features of various OAS configurations.
297–1001–122 Standard 06.01 August 1999
Audible Alarm Cutoff
Alarm Off