Huawei SmartLi-512V-162Ah-F Quick Manual page 6

Advertisement

Item
Description
Specifies the SmartLi connection scenario.
Application scenario
Currently, the UPS and EHU scenarios are
supported.
When the SmartLi is connected to the UPS
without communication, the UPS manages
the SmartLi based on the lead-acid battery
logic. You need to set the number of lead-
acid batteries supported for the UPS on
the SmartLi monitoring screen to ensure
Number of lead-acid
that the charge and discharge operating
batteries supported
voltage ranges of the UPS and SmartLi
(The value of this
match each other.
parameter must be
By default, Number of lead-acid
the same as the
batteries supported is set based on the
setting of Batteries
single battery voltage (2 V). If the single
in a battery string
battery voltage in the UPS system is 12 V,
on the UPS
convert it to 2 V before setting this
monitoring screen.)
parameter. For example, if the single
battery voltage is 12 V and the number of
batteries in a battery string is 42, the value
of Number of lead-acid batteries
supported is 252 (42 x 12/2 = 252) in the
7+7/7+0 scenario.
Specifies the number of battery cabinets
connected in parallel.
Battery cabinet
Currently, a maximum of 10 lithium
quantity
battery cabinets can be connected in
parallel.
Set this parameter based on the altitude of
Altitude (m)
the place where the rack is used.
You can set a charge current limit. The
Chg. cur. limiting
limiting coefficient is a multiple of the
coef. (C)
battery capacity.
Cell undervoltage
You can adjust the end-of-discharge (EOD)
protection threshold
threshold as required.
(V)
Battery
Specifies the maximum battery discharge
undervoltage
time.
protection time (h)
Maintenance period
Specifies the interval for reminding users
(y)
of battery maintenance.
After the maintenance is complete, you
Last maintained at
can set the time as a reference for the
next maintenance.
5. After the green indicator of the BCU blinks at super short intervals and the red indicator is
steady on, switch on the battery circuit breaker on the battery cabinet.
The preceding procedure applies to the single-cabinet scenario. For the multi-cabinet
scenario, see
SmartLi 3.0 User Manual (Short-Term Backup Power)
SmartLi 3.0 Quick Guide (Short-Term Backup Power)
08
Default Value Value Range
Power-Off
UPS, HVDC,
UPS
Switch off the battery circuit breaker in the battery cabinet. (If multiple
EHU, SST
SmartLi cabinets are connected in parallel, perform this operation on
8+8/8+0
8+8/8+0
scenario: 276–
scenario: 276
300
Press and hold the POWER ON/OFF button on the BCU for more than 5s until
7+7/7+0
all the three indicators blink to power off the system. (If multiple SmartLi
7+7/7+0
scenario: 240–
cabinets are connected in parallel, perform this operation on each cabinet.)
scenario: 252
270
If battery modules will be stored for a long time after power-off, remove the BCU to
reduce battery discharge. This prevents battery modules from being overdischarged due
to storage at low SOC.
If battery modules are stored without being fully charged, charge them according to the
6+6/6+0
6+6/6+0
requirements in "Operations > Recharge Requirements for Batteries with Low SOC" to
scenario: 204
scenario: 192–
prevent battery module damage due to overdischarge.
234
When you hold the button to power off a cabinet, only the indicators on the cabinet
where the software version is later than V500R022C00SPC100 will blink.
1
1–10
≤ 1000, 1000–
2000, 2000–
≤ 1000
3000, 3000–
4000
0.5
0.05–1.00
2.7
2.5–2.8
8
8–3000
0
0–10
-
-
.
each cabinet.)
6
Copyright © Huawei Digital Power Technologies Co., Ltd.
2022. All rights reserved.