Component Thicknesses, Component Spacings And Insulation Spacings - OBO Bettermann PYROPLUG MagicBox Mounting Instructions

Table of Contents

Advertisement

Installation requirements, PYROPLUG® MagicBox
6 1 2
6 2
Item
Designation
1
Component thickness
2
Insulation thickness (corresponds to the housing length)
Ring gap around the PYROPLUG
3
nent opening
Spacing of the installations within the PYROPLUG
4
MagicBox
5
Distance to other openings and installations
10 | EN
3-sided PYROPLUG
®
1
Abb 4:
Installation situation, 3-sided PYROPLUG
– Flush to raw floor
– Ceiling insulation above rising section
– Group arrangement position (max. 2 next to each other)
Component thicknesses, component spacings and
insulation spacings
Abb 5:
Insulation distances to other components or component openings
MagicBox in the compo-
®
Tab 2: Insulation distances to other components or component openings
*Exceptions e.g. for hydraulic hoses – see approval
MagicBox
2
MagicBox
®
1
2
4
5
Wall (mm)
≥ 100
300
≤ 10
®
0*
≥ 200
3
3
2
1
3
Ceiling (mm)
≥ 150
300
≤ 30
0*
≥ 200
OBO Bettermann