9
Installation
Classification
Indoor unit (ⓑ)
Classification
Indoor unit (ⓑ)
Number of units
Model name of
indoor unit
4way cassette
4
(AM071FN4DEH✴)
Slim duct
2
(AM056FNLDEH✴)
Slim duct
1
(AM045FNLDEH✴)
1way cassette
1
(AM036FN1DEH✴)
Number of units
Model name of
indoor unit
4way cassette
5
(AM071FN4DEH✴)
4way cassette
2
(AM112FN4DEH✴)
Neo forte
1
(AM028FNTDEH✴)
MCU
2
① ②
Amount of
Unit amount of
additional
refrigerant (kg/EA)
refrigerant (kg)
①×②
0.45
1.80
0.35
0.70
0.35
0.35
0.25
0.25
① ②
Amount of
Unit amount of
additional
refrigerant (kg/EA)
refrigerant (kg)
①×②
0.45
2.25
0.57
1.14
0.27
0.27
0.5
1
① ②
Total amount
of additional
refrigerant (kg)
∑(①×②)
ⓑ 3.10
① ②
Total amount
of additional
refrigerant (kg)
∑(①×②)
ⓑ 4.66