Download Print this page

Samsung AM JXVHGH EU Series Technical Data Book page 90

Vrf dvm s outdoor unit for europe 2layer, 50hz, h/p / h/r high eer type, h/p standard type

Advertisement

9
Installation
Indoor unit capacity (kW)
6.0 kW and below
7.1 kW ~ 16.0 kW and below
20.0 kW ~ 23.0 kW and below
Over 23.0 kW
Classification
Y-joint for outdoor unit (C)
Classification
Y-joint (D)
Classification
Y-joint (E)
Classification
Distribution header (E)
Pipe size (O.D. mm)
Liquid pipe
Ø 6.35
Ø 9.52
Ø 9.52
Ø 9.52
Model name
MXJ-TA3419M
MXJ-TA4122M
Outdoor unit capacity (kW)
40.0 kW and below
45.0 kW
50.4 kW ~ 67.2 kW
73.6 kW ~ 95.2 kW
101.6 kW ~ 135.2 kW
140.2 kW and over
Model name
MXJ-YA1509M
MXJ-YA2512M
Over 15.0 kW ~ 40.0 kW and below
MXJ-YA2812M
Over 40.0 kW ~ 45.0 kW and below
MXJ-YA2815M
Over 45.0 kW ~ 70.3 kW and below
MXJ-YA3419M
Over 70.3 kW ~ 98.4 kW and below
MXJ-YA4119M
Over 98.4 kW ~ 135.2 kW and below
MXJ-YA4422M
Model name
MXJ-HA2512M
MXJ-HA3115M
MXJ-HA3819M
Gas pipe
Ø 12.70
Ø 15.88
Ø 19.05
Ø 22.22
Specification (kW)
135.2 kW and below
Over 140.2 kW
Model name of the branch joint
MXJ-YA2512M
MXJ-YA2812M
MXJ-YA2815M
MXJ-YA3419M
MXJ-YA4119M
MXJ-YA4422M
Specification (kW)
15.0 kW and below
Over 135.
2kW
Specification (kW)
45.0 kW and below (for 4 rooms)
70.3 kW and below (for 8 rooms)
Over 70.3 kW ~ 135.2 kW and below
(for 8 rooms)
90

Advertisement

loading

This manual is also suitable for:

Am hxvagh eu seriesAm jxvagh eu seriesAm jxvhgr eu seriesAm240jxvhgh1euAm260jxvhgh1euAm280jxvhgh1eu ... Show all