Download Print this page

Samsung AM JXVHGH EU Series Technical Data Book page 20

Vrf dvm s outdoor unit for europe 2layer, 50hz, h/p / h/r high eer type, h/p standard type

Advertisement

2
Specifications
Outdoor
Type
Model Name
Power Supply
Mode
HP
Cooling
Performance
Capacity
(Nominal)
Heating
Cooling 1)
Power Input
(Nominal)
Heating 2)
Current
Cooling 1)
Power
Input
Heating 2)
(Nominal)
MCA
MFA
EER (Nominal Cooling)
COP (Nominal Heating)
COP
Energy Grade
Type
Output
Compressor
Model Name
Oil
Type
Type
Output x n
Fan
Air Flow Rate
External
Max.
Static
Liquid Pipe
Gas Pipe
Piping
Discharge Gas Pipe
Connections
Max. Length
Installation
Limitation
Max. Height
Power Source Wire
Field Wiring
Transmission Cable
Type
Refrigerant
Factory Charging
Pressure
Sound
Power
Net Weight
Shipping Weight
External
Dimension
Net Dimensions (WxHxD)
Shipping Dimensions
(WxHxD)
Cooling
Operating
Heating
Temp.
* Specifications may be subject to change without prior notice.
1)
Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2)
Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3)
Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
4)
These products contain R410A which is fluorinated greenhouse gas.
5)
If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
* PDM kit: Pressure Drop Modulation kit
: H/P - High EER type
DVM S(NEW)
AM580JXVHGH1EU
Ø, #, V, Hz
3,4,380-415,50
-
HP
HP
58.00
kW
163.20
Btu/h
556,900
kW
183.60
Btu/h
626,500
kW
42.05
kW
41.44
A
67.50
A
66.40
A
114.00
A
125.00
-
3.88
-
4.43
-
ESEER 6.52
-
-
SSC Scroll x 5
-
kW x n
(6.39) + (6.39x2)x2
-
DS-GB066FAVBSGx5
PVE
-
Propeller
-
W
(620.0x2)x3
CMM
255.0 + 290.0x2
l/s
4,250.0 + 4,833.3x2
8.00
mmAQ
78.40
Pa
Ø, mm
19.05
Ø, inch
3/4"
Ø, mm
41.28
Ø, inch
1 5/8"
Ø, mm
-
Ø, inch
-
m
200 (220)
m
110 (110)
mm²
-
mm²
0.75 ~ 1.50
-
R410A
kg
24.50
69.00
dBA
91.00
231.0 + 296.0x2
kg
kg
250.0 + 315.0x2
mm
(1,295x1,695x765)x3
mm
(1,363x1,887x832)x3
ºC
-5.0 ~ 48.0
ºC
-25.0 ~ 24.0
DVM S(NEW)
DVM S(NEW)
AM600JXVHGH1EU
AM620JXVHGH1EU
3,4,380-415,50
3,4,380-415,50
HP
60.00
62.00
168.20
173.60
573,900
592,300
189.00
195.30
644,900
666,400
42.42
41.85
42.47
42.06
68.10
67.10
68.00
67.40
121.00
129.50
150.00
150.00
3.97
4.45
ESEER 6.45
ESEER 6.54
-
SSC Scroll x 6
SSC Scroll x 6
(4.39x2) + (6.39x2)x2
(6.39x2) + (6.39x2)x2
DS-GA046FAVASGx2 +
DS-GB066FAVBSGx6
DS-GB066FAVBSGx4
PVE
PVE
Propeller
Propeller
(620.0x2)x3
(620.0x2)x3
255.0 + 290.0x2
290.0x3
4,250.0 + 4,833.3x2
4,833.3x3
8.00
78.40
78.40
19.05
22.22
3/4"
41.28
53.98
1 5/8"
2 1/8"
-
-
200 (220)
200 (220)
110 (110)
110 (110)
-
0.75 ~ 1.50
0.75 ~ 1.50
R410A
R410A
24.50
25.20
69.00
69.00
92.00
92.00
262.0 + 296.0x2
296.0x3
281.0 + 315.0x2
315.0x3
(1,295x1,695x765)x3
(1,295x1,695x765)x3
(1,363x1,887x832)x3
(1,363x1,887x832)x3
-5.0 ~ 48.0
-5.0 ~ 48.0
-25.0 ~ 24.0
-25.0 ~ 24.0
DVM S(NEW)
AM640JXVHGH1EU
3,4,380-415,50
HP
HP
64.00
179.20
611,500
201.60
687,900
44.55
44.82
71.50
71.80
131.50
150.00
4.15
4.02
4.64
4.50
ESEER 6.43
-
-
SSC Scroll x 6
(6.39x2)x2 + (6.39x2)
DS-GB066FAVBSGx6
PVE
Propeller
(620.0x2)x3
290.0x3
4,833.3x3
8.00
8.00
78.40
22.22
7/8"
7/8"
53.98
2 1/8"
-
-
-
-
200 (220)
110 (110)
-
-
0.75 ~ 1.50
R410A
25.20
69.00
92.00
296.0x3
315.0x3
(1,295x1,695x765)x3
(1,363x1,887x832)x3
-5.0 ~ 48.0
-25.0 ~ 24.0
20

Advertisement

loading

This manual is also suitable for:

Am hxvagh eu seriesAm jxvagh eu seriesAm jxvhgr eu seriesAm240jxvhgh1euAm260jxvhgh1euAm280jxvhgh1eu ... Show all