Samsung AM JXVHGH EU Series Technical Data Book page 89

Vrf dvm s outdoor unit for europe 2layer, 50hz, h/p / h/r high eer type, h/p standard type

Advertisement

9
Installation
Outdoor unit capacity (kW)
22.4 kW
28.0 kW
33.6 kW
40.0 kW
45.0 kW
50.4 kW
56.0 kW
61.6 kW
67.2 kW
72.8 kW ~ 84.0 kW
89.6 kW ~ 95.2 kW
101.6 kW
106.6 kW ~ 135.2 kW
140.2 kW ~ 168.2 kW
173.6 kW ~ 224.8 kW
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit
Indoor unit capacity (kW)
15.0 kW and below
Over 15.0 kW ~ 22.4 kW and below
Over 22.4 kW ~ 28.1 kW and below
Over 28.1 kW ~ 40.0 kW and below
Over 40.0 kW ~ 45.0 kW and below
Over 45.0 kW ~ 63.3 kW and below
Over 63.3 kW ~ 70.3 kW and below
Over 70.3 kW ~ 98.4 kW and below
Over 98.4 kW ~ 135.2 kW and below
Over 135.2 kW ~ 169.0 kW and below
Over 169.0 kW
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.
*Maximum pipe length within 90m
(Main pipe diameter)
Liquid pipe (mm)
gas pipe (mm)
Ø 19.05
Ø 9.52
Ø 22.22
Ø 12.70
Ø 28.58
Ø 15.88
Ø 34.92
Ø 19.05
Ø 41.28
Ø 22.22
Ø 53.98
Branch pipe length within 45m
Liquid pipe (mm)
Gas pipe (mm)
Ø 15.88
Ø 9.52
Ø 19.05
Ø 22.22
Ø 12.70
Ø 28.58
Ø 15.88
Ø 34.92
Ø 19.05
Ø 41.28
Ø 22.22
Ø 53.98
28 pipe.
*Maximum pipe length over 90m
(Main pipe diameter)
Liquid pipe (mm)
gas pipe (mm)
Ø 22.22
Ø 12.70
note1)
Ø 25.40
Ø 28.58
Ø 15.88
note2)
Ø 31.75
Ø 19.05
note3)
Ø 38.10
Ø 22.22
Ø 41.28
Ø 53.98
note1)
Ø 25.40
Branch pipe length between 45~90m
Liquid pipe (mm)
Gas pipe (mm)
Ø 19.05
Ø 12.70
Ø 22.22
note1)
Ø 25.40
Ø 28.58
Ø 15.88
note2)
Ø 31.75
Ø 19.05
Ø 38.10
note3)
Ø 22.22
Ø 41.28
Ø 53.98
Ø 25.40
note1)
89