2 - Installation
The hearth must be a minimum of 12mm thick fibre cement sheeting, ie Bellis board or equivalent,
with Thermal resistivity of 0.1m2.K/W for 9mm thick sheets. The sheet must be underneath the
appliance and minimum requirement in front of the cooker is 1120mm wide and 300mm in front,
with 200mm included to the left of the firebox door opening.
PLAN VIEW
Combustible Wall
The installation alcove must be lined with 50mm Skamol enclosure board for insulation, and a 20mm
air gap between the cooker and the Skamol board (or 70mm to the combustible wall). For building
out dimensions see the dimensions on page 12. The board must be on all combustible walls to the
sides and to the rear of the appliance to a minimum height of 2m from the floor.
FRONT ELEVATION
Combustible wall
Skamol must start from the floor and continue to a height
of 2m above the floor.
Installation into a double brick wall alcove would need to
be equivalent to an open brick fireplace – see the Building
Code of Australia - BCA or NCC for details.