5523951-CTG-J-0620
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
INDOOR COIL (°F)
60
47
40
30
17
10
0
-10
-20
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Yellow shaded cells are AHRI High Heating conditions.
Orange shaded cells are AHRI Low Heating conditions.
Multipliers for determining the performance with other indoor sections.
COIL MULTIPLIERS - 5 TON
Air Handler
Coil
AE60DBG21
–
AE60DX21
–
AVC60DX21
–
ME20DN21
CF/CM64D
MVC20DN21
CF/CM64D
190
TH4B6022S
AIR TEMP.
ENTERING
MBH
60
70.3
70
68.7
80
67.1
60
60.5
70
59.2
80
57.9
60
55.1
70
54.1
80
53.1
60
48.0
70
46.8
80
45.6
60
40.2
70
39.3
80
38.5
60
35.9
70
35.2
80
34.4
60
29.2
70
28.6
80
28.0
60
19.9
70
19.4
80
19.0
60
13.1
70
12.8
80
12.5
T.C.
S.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.01
1600
COP
KW
MBH
4.89
4.21
71.2
4.32
4.66
69.6
3.85
5.11
68.0
4.46
3.97
61.3
3.94
4.40
60.1
3.52
4.82
58.8
4.19
3.85
55.8
3.71
4.27
54.8
3.32
4.69
53.9
3.79
3.71
48.2
3.35
4.10
46.6
2.98
4.49
45.1
3.33
3.54
40.8
2.95
3.91
40.1
2.64
4.27
39.5
3.06
3.44
36.3
2.71
3.80
35.6
2.42
4.16
34.9
2.57
3.33
29.5
2.28
3.68
29.0
2.04
4.03
28.4
1.80
3.22
20.1
1.60
3.56
19.7
1.43
3.90
19.3
1.24
3.10
13.2
1.10
3.42
13.0
0.98
3.74
12.7
KW
1.00
1.00
1.00
1.00
0.99
ID CFM
1850
COP
KW
MBH
5.14
4.06
72.2
4.54
4.49
70.5
4.06
4.91
68.8
4.66
3.86
62.2
4.12
4.27
61.0
3.68
4.68
59.8
4.34
3.76
56.5
3.85
4.17
55.5
3.45
4.58
54.6
3.88
3.64
48.4
3.40
4.02
46.5
3.01
4.39
44.5
3.39
3.52
41.3
3.02
3.89
40.9
2.72
4.26
40.5
3.10
3.43
36.74
2.76
3.78
36.1
2.48
4.13
35.4
2.61
3.32
29.9
2.32
3.66
29.3
2.08
4.00
28.8
1.83
3.21
20.3
1.63
3.54
19.9
1.46
3.87
19.6
1.26
3.09
13.4
1.12
3.40
13.1
1.00
3.72
12.9
Johnson Controls Ducted Systems
2100
COP
KW
5.39
3.91
4.76
4.32
4.26
4.71
4.85
3.75
4.30
4.14
3.85
4.54
4.50
3.67
3.99
4.07
3.57
4.47
3.97
3.57
3.45
3.94
3.04
4.29
3.46
3.50
3.10
3.87
2.79
4.25
3.15
3.42
2.81
3.76
2.53
4.10
2.64
3.31
2.36
3.64
2.13
3.97
1.86
3.20
1.66
3.52
1.49
3.84
1.27
3.08
1.14
3.38
1.02
3.69