Diagnostics Info; Diagnostics Mapping - Real Time Automation 460SCQT-N2E Product User Manual

Protocol gateway
Table of Contents

Advertisement

Diagnostics Info

The Diagnostics page is where you can view both protocols' diagnostics information, # of Data
Mappings, # of String Mapping and # Alarm Mappings.
For protocol specific diagnostic information, refer to the next few pages.

Diagnostics Mapping

This section displays the number of mappings that are enabled, Data Mapping and String Mapping will
show the # of Errors and First Errors. Alarms will show # active and Last Alarm that was active.
Common Errors:
1) Destination or Source Point does not exist
a) Solution: Re-map the mapping
2) Source or Destination Pointer too small
a) There is not enough space on either the
Source, or the Destination for the data
you want to copy. This is typically seen
when the Destination is smaller than
the amount of data being transferred to
it.
3) Range Discard, Min or Max Value
a) The actual data value is outside of the
defined range
4) Math Error
a) Operation value cannot be 0
5) Scaling Error
a) Source Min must be smaller than Source Max
b) Destination Min must be smaller than Destination Max
Real Time Automation, Inc.
Note: you can also view this
information on the Main Page.
76
1-800-249-1612

Advertisement

Table of Contents
loading

Table of Contents