Mitsubishi Heavy Industries FDT90VNPWVH Service Manual page 59

Standard inverter packaged air-conditioners
Hide thumbs Also See for FDT90VNPWVH:
Table of Contents

Advertisement

'19 • PAC-SM-334
9)Disconect the cable of terminal block and fuse.(Fig.4 ⑦、⑧)
10)Disconnect the cables of reactor.(Fig.4 ⑨)
Fig.4 Cable of fuse, terminal block and reactor
11)Disconnect 2 earth calbes on right side of control box.(Fig.5 ⑩、⑪)
Fig.5 Earth cable of control box
12)Disconnect CnTH(Black) on control PCB. (Fig.6 ⑫)
13)Disconnect a power cable of compressor(U,V,W) from control PCB.(Fig.6 ⑬)
Fig.6 CnTH and power cable of compressor(U,V,W)
14)Take a control PCB out. (Fig.7)
  Note: When you take a control box out, please pull it up straight.
Otherwise, it can be damaged.
Fig.7 How to remove control PCB