Mitsubishi Heavy Industries FDTC25VH1 Service Manual

Mitsubishi Heavy Industries FDTC25VH1 Service Manual

Inverter residential air to air heat pump type
Hide thumbs Also See for FDTC25VH1:

Advertisement

SERVICE MANUAL
INVERTER RESIDENTIAL
AIR-CONDITIONERS
(Split system, air to air heat pump type)
Ceiling concealed type
SRR25ZS-W
SRR35ZS-W
4-way ceiling cassette type
FDTC25VH1
FDTC35VH1
SM-
285

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FDTC25VH1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Mitsubishi Heavy Industries FDTC25VH1

  • Page 1 SERVICE MANUAL INVERTER RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) Ceiling concealed type SRR25ZS-W SRR35ZS-W 4-way ceiling cassette type FDTC25VH1 FDTC35VH1...
  • Page 2 (14) Outline of automatic operation ............(15) Protective control function ..............1.2 Models FDTC25VH1, 35VH1 ..............15 1.2.1 Remote control (option parts) ............... 15 1.2.2 Operation control function by the wired remote control ......18 1.2.3 Operation control function by the indoor control........21 1.2.4 Operation control function by the outdoor control.........
  • Page 3 '20 • SR-SM-285 2.2 FDTC series ....................67 2.2.1 Diagnosing of microcomputer circuit ..........67 (1) Selfdiagnosis function ................67 (2) Troubleshooting procedure ..............70 ............70 (3) Troubleshooting at the indoor unit (4) Troubleshooting at the outdoor unit ............73 (5) Check of anomalous operation data with the remote control ....
  • Page 4 '20 • SR-SM-285 1. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER 1.1 Models SRR25ZS-W, 35ZS-W (1) Operation control function by wireless remote control Operation section Transmission section OPERATION MODE select button ON/OFF (luminous) button Each time the button is pressed, the mode changes.
  • Page 5 TIMER light (yellow) Illuminates during TIMER operation. '20 • SR-SM-285 (2) Unit ON/OFF button When the wireless remote control batteries become weak, or if the wireless remote control is lost or malfunctioning, this but- ton may be used to turn the unit on and off. (a) Operation Push the button once to place the unit in the automatic mode.
  • Page 6 '20 • SR-SM-285 (5) Selection of the annual cooling function (a) The annual cooling control is valid from factory default setting. It is possible to disable by cutting jumper wire (J172), or changing the setting of DIP switch (SW2-4) on the interface kit (option) PCB if it is connected. Interface kit Jumper wire (SC-BIKN2-E)
  • Page 7 '20 • SR-SM-285 (8) Timer operation (a) Comfortable timer setting (ON timer) If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the relationship between the indoor temperature at the setting time (temperature of room tempera- ture sensor) and the setting temperature.
  • Page 8 '20 • SR-SM-285 (c) Defrost operation (i) Starting conditions (Defrost operation can be started only when all of the following conditions are satisfied.) 1) After start of heating operation When it elapsed 35 minutes (Accumulated compressor operation time) 2) After end of defrost operation When it elapsed 35 minutes (Accumulated compressor operation time) 3) Outdoor heat exchanger temperature sensor (TH2) When the temperature has been below –5ºC for 3 minutes continuously...
  • Page 9 '20 • SR-SM-285 (12) Outline of cooling operation (a) Operation of major functional components in cooling mode Cooling Thermostat ON Thermostat OFF Failure Compressor Indoor fan motor Outdoor fan motor (few minutes ON) (few minutes ON) 4-way valve (b) Detail of control in each mode (Pattern) (i) Fuzzy operation During the fuzzy operation, the air flow and the compressor speed are controlled by calculating the difference be- tween the indoor temperature setting correction temperature and the retum air temperature.
  • Page 10 '20 • SR-SM-285 (14) Outline of automatic operation (a) Determination of operation mode The unit checks the indoor air temperature and the outdoor air temperature, determines the operation mode, and then be- gins in the automatic operation. Cooling 27.5 25.5 Dehumidifying Indoor air temperature (˚C) 19.5...
  • Page 11 2.5–5 (iii) Reset conditions 5–8 '20 • SR-SM-285 (iii) Reset conditions (b) Cooling overload protective control ( i ) Operating conditions When the outdoor air temperature (TH3) has become continuously for 30 seconds at 41°C or more, or (2) Cooling overload protective control 47ºC or more with the compressor running, the lower limit speed of compressor is brought up.
  • Page 12 '20 • SR-SM-285 Upper 3 Lower 3 ●Values of A, B, C, D, E, F Upper 2 Lower 2 Outdoor air temperature (˚C) Upper 1 Lower 1 First time After the second times Outdoor air temperature (°C) Range A Compressor speed: Upper/lower limit (rps) Lower 1 Range B Upper 1...
  • Page 13 '20 • SR-SM-285 (iii) Reset condition When the outdoor air temperature drops below 21ºC (g) Heating low outdoor temperature protective control (i) Protective control I 1)  Operating conditions   2)  Detail of operation    changed as shown in the figure below. Lower limit 45 rps Lower limit 40 rps Normal operation...
  • Page 14 '20 • SR-SM-285 ( j ) Current cut (i) Purpose Inverter is protected from overcurrent. (ii) Detail of operation Output current from the inverter is monitored with a shunt resistor and, if the current exceeds the setting value, the com- pressor is stopped immediately.
  • Page 15 '20 • SR-SM-285 3) Reset conditions When either of the following conditions is satisfied a) The outdoor air temperature (TH3) is 25ºC or higher. b) The compressor command speed is 0 rps. (ii) Heating 1) Operating conditions When the outdoor air temperature (TH3) is 0ºC or lower continues for 30 seconds while the compressor command speed is other than 0 rps.
  • Page 16 '16 • PAC-T-251 '20 • SR-SM-285 1.10 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER 1.2 Models FDTC25VH1, 35VH1 1.10.1 Remote control 1.2.1 Remote control (Option parts) Wired remote control (1) Wired remote control Model RC-EX3A Model RC-EX3A ⑤ LCD (with backlight) ③...
  • Page 17 '20 • SR-SM-285 Wired remote control Wired remote control Model RC-E5 Model RC-E5 The figure below shows the remote control with the cover opened. Note that all the items that may be displayed in The figure below shows the remote control with the cover opened. Note that all the items that may be displayed in the liquid crystal display area are shown in the figure for the sake of explanation.
  • Page 18 '20 • SR-SM-285 '16 • PAC-T-251 '16 • PAC-T-251 Wireless remote control Wireless remote control (2) Wireless remote control RCN-E2 Indication section Indication section ① OPERATION MODE display Indicates selected operation mode. SET TEMP display Indicates set temperature. SLEEP TIMER time display Indicates the amount of time remaining on the sleep timer.
  • Page 19 '16 • PAC-T-251 '20 • SR-SM-285 1.10.2 Operation control function by the wired remote control 1.2.2 Operation control function by the wired remote control ●Model RC-EX3A (1) Switching sequence of the operation mode switches of remote control (a) Tap the change operation mode button on the TOP screen. (b) When the change operation mode screen is displayed, tap the button of desired mode.
  • Page 20 '20 • SR-SM-285 ●Content memorized with the power failure compensation are as follows. Note(1) Items (f) and (g) are memorized regardless whether the power failure compensation is effective or not while the setting of silent mode is cancelled regardless whether the power failure compensation is effective or not. At power failure –...
  • Page 21 '20 • SR-SM-285 ● Model RC-E5 (1) Switching sequence of the operation mode switches of remote control COOL HEAT AUTO (2) CPU reset This functions when “CHECK” and “ESP” buttons on the remote control are pressed simultaneously. Operation is same as that of the power source reset.
  • Page 22 '20 • SR-SM-285 1.2.3 Operation control function by the indoor control (1) Auto operation (a) If “Auto” mode is selected by the remote control, the heating and the cooling are automatically switched according to the difference between outdoor air temperature and setting temperature and the difference between setting temperature and return air temperature.
  • Page 23 '16 • PAC-T-251 '20 • SR-SM-285 (ii) Regardless of the setting temperature, the cooling or heating operation mode is judged according to the "Judgment based on Room temperature/Cooling or Heating and Outdoor temperature/Cooling or Heating". 1) In case of "Room temperature/Cooling < Indoor return air temperature" and "Outdoor temperature/Cooling < Outdoor ⇒...
  • Page 24 '20 • SR-SM-285 (4) Timer operation (a) RC-EX3A (i) Sleep timer Set the time from the start to stop of operation. The time can be selected in the range from 30 to 240 minutes (in the unit of 10-minute). Note (1) Enable the “Sleep timer” setting from the remote control. If the setting is enabled, the timer operates at every time. (ii) Set OFF timer by hour Set the time to stop the unit after operation, in the range from 1 to 12 hours (in the unit of hour).
  • Page 25 '20 • SR-SM-285 (5) Hot start (Cold draft prevention at heating) (a) Operating conditions When either one of following conditions is satisfied, the hot start control is performed. (i) From stop to heating operation (ii) From cooling to heating operation (iii) Form heating thermostat OFF to ON (iv) After completing the defrost operation (only on units with thermostat ON) (b) Contents of operation...
  • Page 26 '20 • SR-SM-285 (7) Auto swing control Note Even if [Auto Swing] is selected, the louver position with anti draft function is fixed to position 1. (a) RC-EX3A (i) Louver control 1) To operate the swing louver when the air-conditioner is operating, press the “Direction” button on the TOP screen of remote control.
  • Page 27 '20 • SR-SM-285 (8) Thermostat operation (a) Cooling (i) Thermostat is operated with the room temperature control. (ii) Thermostat is turned ON or OFF relative to the setting room temperature as shown below. Thermostat ON Temperature drop Thermostat OFF Temperature rise Setting room temperature (iii) Thermostat is turned ON when the room temperature is in the range of -1 <...
  • Page 28 '20 • SR-SM-285 (d) Fan control during cooling thermostat OFF (i) Following fan controls during the cooling thermostat OFF can be selected with the indoor function setting of the wired remote control. ① Low fanspeed, ② Set fan speed (Factory default), ③ Intermittence, ④ Fan OFF (ii) When the “Low fan speed”...
  • Page 29 '20 • SR-SM-285 (11) Drain pump control (a) This control is operated when the inverter frequency is other than 0 Hz during the cooling operation and automatic cooling and dehumidifying operations. (b) Drain pump ON condition continues for 5 minutes even when it enters the OFF range according to (i) above after turning the drain pump ON, and then stops.
  • Page 30 '20 • SR-SM-285 (c) Operation check mode There is no communication with the outdoor unit but it allows performing operation in respective modes by operating the remote control. (d) Drain pump test run mode As the drain pump test run is established, the drain pump only operates and during the operation protective functions by the microcomputer of indoor unit become ineffective.
  • Page 31 '20 • SR-SM-285 (17) Plural unit control – Control of 16 units group by one remote control (a) Function One remote control can control a group of multiple number of unit (Max. 16 indoor units). “Operation mode” which is set by the remote control can operate or stop all units in the group one after another in the order of unit. No. Thermostat and protective function of each unit function independently.
  • Page 32 '20 • SR-SM-285 (19) Abnormal temperature sensor (return air/indoor heat exchanger) broken wire/short-circuit detection (a) Broken wire detection When the return air temperature sensor detects -55°C or lower or the heat exchanger temperature sensor detect -55°C or lower for 5 seconds continuously, the compressor stops. After a 3-minute delay, the compressor restarts but, if it is detected again within 60 minutes after the initial detection for 6 minutes continuously, stops again (the return air temperature sensor : E7, the heat exchanger temperature sensor : E6).
  • Page 33 '20 • SR-SM-285 (b) Input for external control The external input for the indoor unit can be selected from the following input. Input name Content 1 Run/Stop Refer to [(20) (c) Remote operation input] 2 Premission/Prohibition Refer to [(21) Operation permission/prohibition] 3 Cooling/Heating Refer to [(23) Selection of cooling/heating external input function] 4 Emergency stop...
  • Page 34 '20 • SR-SM-285 Individual operation (Factory default) All units operation (Local setting) Only the unit Only the unit All units in one All units in one directly connected CnT-6 or directly connected remote control remote control to the remote CnTA to the remote control system can be system can be...
  • Page 35 '20 • SR-SM-285 (a) In case of CnT ① Operation stop level > CnTA ③ Operation permission/prohibition level Operation Operation Operation Stop Stop Stop Level input Operation permission Operation permission CnTA Operation prohibition Operation permission/ prohibition setting Operation Operation( ) Operation Stop Stop...
  • Page 36 '20 • SR-SM-285 (22) Temporary stop input In case of temporary stop, operation lamp of remote control lights, but indoor/outdoor unit stop the operation. (a) In case of “level input” setting (Factory default) Input signal to CnT-6 or CnTA is OFF → ON : Temporary stop Input signal to CnT-6 or CnTA is OFF →...
  • Page 37 '20 • SR-SM-285 (24) Fan control at heating startup (a) Starting conditions At the start of heating operation and after the end of hot start control, if the difference of setting temperature and return air temperature is 5°C or higher, this control is performed. (b) Contents of control (i) Sampling is made at each minute and, when the indoor heat exchanger temperature (detected with Thi-R) is 37°C or higher, present number of revolutions of indoor fan speed is increased by 10min...
  • Page 38 '20 • SR-SM-285 (32) Fan circulator operation (RC-EX3A only) When the fan is used for circulation, the unit is operated as follows depending on the setting with the remote control. (a) If the invalid is selected with the remote control, the fan is operated continuously during the fan operation. (normal fan mode) (b) If the valid is selected with the remote control, the fan is operated or stopped when on the difference of the remote control temperature sensor and the return air temperature sensor becomes bigger than 3°C.
  • Page 39 '20 • SR-SM-285 (37) Motion sensor control (RC-EX3A and RCN-E2 only) The sensor determines the presence of people and the amount of activity, and the following controls are done by the motion sensor. Following settings are necessary to activate motion sensor control. (a) Infrared (motion) sensor setting: Installation setting of remote control RC-EX3A The indoor unit which is set to “Enable”...
  • Page 40 '20 • SR-SM-285 (i) Power saving / comfort control The setting temperature is adjusted according to the presence of people and their amount of activity detected by the infrared (motion) sensor. MODE:AUTO/COOL/HEAT mode operation Heat Source & Activity High None Normal When the extent of human 33ºC...
  • Page 41 '20 • SR-SM-285 1.2.4 Operation control function by the outdoor control (1) Defrost operation (a) Starting conditions (Defrosting operation can be started only when all of the following conditions are satisfied.) 1) After start of heating operation When it elapsed 35 minutes. (Accumulated compressor operation time) 2) After end of defrosting operation When it elapsed 35 minutes.
  • Page 42 '20 • SR-SM-285 (b) Detail of operation 1) The outdoor fan is stepped up by 3 speed step. (Upper limit 8th speed) 2) The lower limit of compressor command speed is set to 30 or 45 rps and even if the calculated result becomes lower than that after fuzzy calculation, the speed is kept to 30 or 45 rps.
  • Page 43 '20 • SR-SM-285 (c) Reset conditions When either of the following condition is satisfied 1) The outdoor air temperature (TH3) is D ˚C or higher. 2) The compressor command speed is 0 rps. (5) Heating high pressure control Model SRK50 (a) Starting condition When the indoor heart exchanger temperature (Thi-R) has risen to a specified temperature while the compressor is turned on.
  • Page 44 '20 • SR-SM-285 (7) Heating low outdoor temperature protective control (a) Protective control I 1)  Operating conditions   2)  Detail of operation changed as shown in the figure below. Lower limit 45 rps Lower limit 40 rps Normal operation Outdoor air temperature(°C ) 3) Reset conditions (8) Compressor overheat protection (a) Purpose...
  • Page 45 '20 • SR-SM-285 (10) Current cut (a) Purpose Inverter is protected from overcurrent. (b) Detail of operation Output current from the inverter is monitored with a shunt resistor and, if the current exceeds the setting value, the compressor is stopped immediately. Operation starts again after a delay time of 3 minutes. (11) Outdoor unit failure This is a function for determining when there is trouble with the outdoor unit during air-conditioning.
  • Page 46 '20 • SR-SM-285 (b) Heating 1) Operating conditions When the outdoor air temperature (TH3) is 0ºC or lower continues for 30 seconds while the compressor com- mand speed is other than 0 rps 2) Detail of operation The outdoor fan is stepped up by 2 speed step at each 20 seconds. (Upper limit 8th speed) 3) Reset conditions When either of the following conditions is satisfied a) The outdoor air temperature (TH3) is 2ºC or higher.
  • Page 47 '09•SRK-DB-087D '20 • SR-SM-285 Reference Reference 2. MAINTENANCE DATA 2 TROUBLESHOOTING PROCEDURES FOR ELECTRICAL EQUIPMENT 2.1 SRR series (1) Cautions (2) Items to check before troubleshooting source (3) Troubleshooting procedure (If the air-conditioner does not run at all) satisfied Important source wireless proced-...
  • Page 48 '09•SRK-DB-087D '20 • SR-SM-285 (4) Troubleshooting procedure (If the air-conditioner runs) 49-55. 49-55.
  • Page 49 '20 • SR-SM-285 (5) Self-diagnosis table Wired Indoor unit display panel Description remote Cause Display (flashing) condition control TIMER of trouble display light light When a heat exchanger sensor 1 wire disconnection is detected • Broken heat exchanger sensor 1-time 1 wire, poor connector while operation is stopped.
  • Page 50 '09•SRK-DB-087D '20 • SR-SM-285 (6) Service mode (Trouble mode access function) (a) Explanation of terms Explanation Term The service mode is the mode where service data are displayed by flashing of the display lights Service mode when the operations in item (b) below are performed with the indoor control. These are the contents of error displays and protective stops which occurred in the past in the air- conditioner system.
  • Page 51 '09•SRK-DB-087D '20 • SR-SM-285 4-time flash 2-time flash. wireless mode mode Self-diagnosis data wireless mode mode Wireless remote control setting Contents of output data Operation mode Fan speed mode wireless Indicates the number of Wireless remote control setting occasions previous to the present Temperature setting the error display data are from.
  • Page 52 '09•SRK-DB-087D '20 • SR-SM-285 (Example) Wireless remote control setting Operation Displayed data Fan speed Temperature mode mode setting Displays the reason for the stop (error code) the previous time an error was displayed. 21ºC Displays the reason for the stop (error code) 2 times previous when an error was displayed. 22ºC Cooling 23ºC...
  • Page 53 '09•SRK-DB-087D '20 • SR-SM-285 (c) Error code, stop code table Number of flashes when in service mode Stop coad Error Auto TIMER Error content Cause Occurrence conditions display recovery light Error coad light (10's digit) (1's digit) Normal Error of wired remote control Broken wired remote control wire.
  • Page 54 '09•SRK-DB-087D '20 • SR-SM-285 4-time flash 2-time flash. (d) Operation mode, Fan speed mode information tables (ii) mode mode Display pattern when Display pattern when Fan speed in service mode in service mode Operation mode mode when when there is an there is an RUN light TIMER light...
  • Page 55 '09•SRK-DB-087D '20 • SR-SM-285 (e) Temperatare information (i) Room temperature sensor, indoor heat exchanger temperature sensor, outdoor air temperature sensor, outdoor heat exchanger temperature sensor Unit: °C TIMER light (1’s digit) RUN light (10’s digit) Buzzer sound (sounds for 0.1 second) (does not sound) temperature information Sensor value displayed when the error code is normal...
  • Page 56 '09•SRK-DB-087D '20 • SR-SM-285 (ii) Discharge pipe temperature sensor Unit: °C TIMER light (1’s digit) RUN light (10’s digit) Buzzer sound (sounds for 0.1 second) (does not sound) temperature information Sensor value displayed when the error code is normal -64ºC temperature sensor data 0.1 sec.
  • Page 57 '09•SRK-DB-087D '20 • SR-SM-285 Service data record form Wireless r Operation mode Fan speed mode Wireless r Wireless r Wireless r Wireless r Wireless r wireless...
  • Page 58 '09•SRK-DB-087D '20 • SR-SM-285 (7) Inspection procedures corresponding to detail of trouble Sensor error Broken sensor wire, connector poor connection Temperature sensor characteristics (Room Discharge pipe temperature sensor characteristics temperature, indoor heat exchanger temperature, outdoor heat exchanger temperature, outdoor air temperature) (Short-circuit) (Short-circuit) - 10...
  • Page 59 '09•SRK-DB-087D '20 • SR-SM-285 Current cut Compressor lock, Compressor wiring short-circuit, Compressor output is open phase, Outdoor unit PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty. short-circuit? unit *   Defective outdoor unit PCB * Defective outdoor unit PCB between terminals.
  • Page 60 '09•SRK-DB-087D '20 • SR-SM-285 Over heat of compressor Gas shortage, defective discharge pipe temperature sensor temperature temperature Defective outdoor unit PCB Error of signal transmission Wiring error including power cable, defective indoor/ outdoor unit PCB ② ③ unit ② ③ unit ①...
  • Page 61 '09•SRK-DB-087D '20 • SR-SM-285 Trouble of outdoor unit Insufficient refregerant amount, Faulty power transistor, Broken compressor wire Service valve close, Defective EEV, Defective outdoor unit PCB unit ◆  unit     defrost operation   minutes or more Notes (1) (2) Check resistance between terminals, see page 58. unit between terminals ....
  • Page 62 '20 • SR-SM-285 Rotor lock Defective compressor, defective outdoor unit PCB unit between terminals. See page 58. Service valve (gas side) closed, Service valve (gas side) closed operation (8) Phenomenon observed after shortcircuit, wire breakage on sensor Defective outdoor unit PCB (a) Indoor unit Phenomenon Operation...
  • Page 63 '20 • SR-SM-285 (8) Phenomenon observed after short-circuit, wire breakage on sensor (a) Indoor unit Phenomenon Operation Sensor mode Short-circuit Disconnected wire Cooling Room temperature sensor Heating '09•SRK-DB-087D Freezing cycle system protection trips and stops the compressor. Cooling Heat exchanger temperature sensor '09•SRK-DB-087D Heating...
  • Page 64 Replace indoor unit PCB. blocks ② and ③ oscillating between DC 0 and 20V? '20 • SR-SM-285 Indoor electrical components are normal. (b) Indoor fan motor check procedure 1) Indoor unit PCB output check ① ④ ⑤ DC several V (–) DC 308-336V (4-6 V)
  • Page 65 Operation SW ON Measure in this section '20 • SR-SM-285 (10) How to make sure of wireless remote control wireless wireless wireless wireless wireless wireless   Simplified check method of wireless remote control It is normal if the signal transmission section of the wireless remote control emits a whitish light at each transmission on the monitor of digital camera.
  • Page 66 '20 • SR-SM-285 (12) Outdoor unit inspection points Models SRC25ZS-W1, 35ZS-W1 ◆Check point of outdoor unit WARNING- HIGH VOLTAGE ◆Power source and serial signal inspection High voltage is produced in the control box. Don't touch electrical parts in the control box for 5 minutes after the : AC 220/230/240V unit is stopped.
  • Page 67 '09•SRK-DB-087D '20 • SR-SM-285 (a) Inspection of electronic expansion valve (ii) (iii) unit (iv) • Inspection of electronic expansion valve as a separate unit Measuring point Resistance when normal (b) Outdoor fan motor check procedure unit unit          source ② unit unit Measuring...
  • Page 68 '20 • SR-SM-285 2.2 FDTC series 2.2.1 Diagnosing of microcomputer circuit (1) Selfdiagnosis function (a) Check Indicator Table Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote control error code, indoor unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).
  • Page 69 '20 • SR-SM-285 (ii) Outdoor unit Remote control Indoor unit control PCB Reference Location of trouble Description of trouble Repair method Green Error code Red LED Red LED page Installation, operation status • Higher outdoor heat exchanger temperature Repair Replacement, repair Outdoor heat exchanger Keeps •...
  • Page 70 '20 • SR-SM-285 (iv) Display sequence of error codes or inspection indicator lamps ■ Occurrence of one kind of error Displays are shown respectively according to errors. ■ Occurrence of plural kinds of error Section Category of display • Displays the error of higher priority (When plural errors are persisting) Error code on remote control Red LED on indoor...
  • Page 71 '20 • SR-SM-285 ■ Error log and reset Error indicator Memorized error log Reset • Stop the unit by pressing the ON/OFF Remote control display • Higher priority error is memorized. switch of remote control. • If the unit has recovered from anomaly, it Red LED on indoor unit control PCB •...
  • Page 72 '20 • SR-SM-285 1) Model FDTC series PSC012D050 Replace and set up the PCB according to this instruction. i) Set to an appropriate address and function using switch on PCB.   Select the same setting with the removed PCB. Item Switch Content of control Address...
  • Page 73 '20 • SR-SM-285 ●DIP switch setting list Switch Description Default setting Remark Address No. setting at plural indoor units control by 1 R/C SW6-1 SW6-2 Model selection As per model See table 1. SW6-3 SW6-4 Normal * /Test run Test run, drain pump motor Normal SW7-1 Keep OFF...
  • Page 74 '20 • SR-SM-285 (4) Troubleshooting at the outdoor unit When troubleshooting the outdoor unit, firstly assess the overview of malfunction and try to presume the cause and the faulty part by checking the error code dispalyed on the remote control and then proceed further inspection and remedy it. Self-diagnosis system by microcomputor on indoor unit PCB can assist to find the cause of malfunction smoothly by making a diagnosis of not only the anomaly of microcomputer, but also the anomaly in power source system, installation space, overload resulting from improper charging amount of refrigerant and etc.
  • Page 75 '20 • SR-SM-285 (5) Check of anomalous operation data with the remote control (a) In case of RC-EX3A remote control [Operating procedure] ➀ On the TOP screen, touch the buttons in the order of “Menu” ➝ “Service setting” ➝ “Service & Maintenance” ➝ “Service password”...
  • Page 76 '20 • SR-SM-285 (b) In case of RC-E5 remote control Data Item Number Operation data can be checked with remote control unit operation. (Operation Mode) (Set Temperature) ➀ Press the button. (Return Air Temperature) The display change “ ” (Remote Control Temperature Sensor) ➁...
  • Page 77 '20 • SR-SM-285 (6) Inverter checker for diagnosis of inverter output  ●Checking method 1) Setup procedure of checker a) Power OFF (Turn off the breaker). b) Remove the terminal cover of compressor and disconnect the wires (U, V, W) from compressor. c) Connect the wires U (Red) , V (White) and W (Black) of the checker to the terminal of disconnected wires (U, V, W) from compressor respectively.
  • Page 78 '20 • SR-SM-285 (7) Outdoor unit inspection points Models SRC25ZS-W1, 35ZS-W1 ◆Check point of outdoor unit WARNING- HIGH VOLTAGE ◆Power source and serial signal inspection High voltage is produced in the control box. Don't touch electrical parts in the control box for 5 minutes after the : AC 220/230/240V unit is stopped.
  • Page 79 '20 • SR-SM-285...
  • Page 80: Table Of Contents

    '20 • SR-SM-285 2.2.2 Troubleshooting flow (1) List of troubles Remote control display Description of trouble Reference page None Operates but does not cool. None Operates but does not heat. None Earth leakage breaker activated None Excessive noise/vibration (1/3) None Excessive noise/vibration (2/3) None Excessive noise/vibration (3/3)
  • Page 81: Operates But Does Not Cool

    '20 • SR-SM-285 (2) Troubleshooting Green Error code Content Remote control: None Operates but does not cool Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Check the indoor fan operation. Check the temperature difference between return and supply air.
  • Page 82: Operates But Does Not Heat

    '20 • SR-SM-285 Green Error code Content Remote control: None Operates but does not heat Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Check the indoor fan operation. Check the temperature difference between return and supply air. It is normal.
  • Page 83: Earth Leakage Breaker Activated

    '20 • SR-SM-285 Green Error code Content Remote control: None Earth leakage breaker activated Stays OFF Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are OK the insulation resistance and Replace compressor. resistance between terminals (1) of compressor? (1) 4.428Ω...
  • Page 84: Excessive Noise/Vibration

    '20 • SR-SM-285 Green Error code Content Remote control: None Excessive noise/vibration (1/3) – – Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure If excessive noise/vibration persists when sufficient Does time has elapsed after noise/vibration stopping the unit, it is occur during or soon after stopping operation considered that the air-...
  • Page 85: Excessive Noise/Vibration

    '20 • SR-SM-285 Green Error code Content Remote control: None Excessive noise/vibration (2/3) – – Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure From previous page Rearrange the piping to Are the pipes avoid contact with the contacting the casing.
  • Page 86: Excessive Noise/Vibration

    '20 • SR-SM-285 Green Error code Content Remote control: None Excessive noise/vibration (3/3) – – Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure From previous page If insufficient cooling/ [Adjustment heating problem happens during commissioning] due to anomalous operating Does noise/vibration occur when the conditions at cooling/ cooling/heating operation is in...
  • Page 87: Louver Motor Failure

    '20 • SR-SM-285 Green Error code Content Louver motor failure Remote control: None Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure ▲ Check at the indoor unit side. Operate after waiting for more than 1 minute. Does the louver operate at the power 2.
  • Page 88: Power Source System Error (Power Source To Remote Control)

    '20 • SR-SM-285 Green Error code Content Power source system error Remote control: None (Power source to indoor unit control PCB) Indoor Stays OFF Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure AC220/240V detected between on the terminal block of indoor unit? AC380/415V...
  • Page 89 '20 • SR-SM-285 Green Error code Content Power source system error Remote control: None (Power source to remote control) Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the connection of the Correct. ➞ Insert connector remote control's wiring OK? securely.
  • Page 90: Inspect I/U

    '20 • SR-SM-285 Green Error code Content INSPECT I/U Remote control: INSPECT I/U Keeps flashing Stays OFF Indoor (When 1 or 2 remote controls are connected) 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are 2 units of remote control connected? ⑴,...
  • Page 91: Inspect I/U (Connection Of 3 Units Or More Remote Controls)

    '20 • SR-SM-285 Green Error code Content INSPECT I/U Remote control: INSPECT I/U Keeps flashing Stays OFF Indoor (Connection of 3 units or more remote controls) 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are more than Reduce to 2 units or less. 3 units of remote control connected? Does remote...
  • Page 92: Communication Error At Initial Operation

    '20 • SR-SM-285 Green Error code Content Communication error at Remote control: WAIT initial operation (1/3) Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All Models Diagnosis Countermeasure When the remote control LCD displays “ ” 2 WAIT minutes after the power on The remote control LCD Turn the breaker off once and then...
  • Page 93 '20 • SR-SM-285 Green Error code Content Communication error at Remote control: WAIT initial operation (2/3) Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All Models Diagnosis Countermeasure When the fuse is blown, the method to inspect inverter before replacing the power Is there source fuse...
  • Page 94 '20 • SR-SM-285 Green Error code Content Communication error at Remote control: WAIT initial operation (3/3) Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All Models Diagnosis Countermeasure When the remote control display is extinguished after the power on. Remote control display is extinguished after the power on.
  • Page 95: No Display

    '20 • SR-SM-285 Green Error code Content No display Remote control: None Stays OFF Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Remote control does not display anything after the power on. Is DC10V or Defective remote control higher detected at remote control connection terminals? 2.
  • Page 96 '20 • SR-SM-285 Green Error code Content Remote control Remote control: Keeps flashing Stays OFF Indoor communication circuit error 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is it possible to Malfunction by noise reset normally by the Check peripheral power reset? environment.
  • Page 97 '20 • SR-SM-285 Green Error code Content Remote control: Communication error during operation Keeps flashing 2-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure ● In case that the outdoor unit red LED flashes 2-time Note (1) Inspect faulty connections (disconnection, looseness) on the outdoor unit terminal block.
  • Page 98: When The Temperature Sensor Detects -50°C Or Lower For 5 Seconds Continuously

    '20 • SR-SM-285 Green Error code Content Indoor heat exchanger Remote control: temperature sensor anomaly Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the connection of indoor heat Correct. ➞ Insert connector exchanger temperature sensor securely.
  • Page 99 '20 • SR-SM-285 Green Error code Content Return air temperature Remote control: sensor anomaly Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the connection of return Correct. ➞ Connect air temperature sensor connector. connector OK? 2.
  • Page 100 '20 • SR-SM-285 Green Error code Content Remote control: Heating overload operation Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the air filter clogged? Wash. 2. Error detection method Is the indoor heat exchanger Defective indoor heat temperature sensor exchanger temperature...
  • Page 101 '20 • SR-SM-285 Green Error code Content Drain trouble Remote control: Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Check the error data in the remote control. Is there any overflow? Is DC12V at CNI connector? Check float switch.
  • Page 102: E10 Excessive Number Of Connected Indoor Units (More Than 17 Units) By Controlling With One Remote Control

    '20 • SR-SM-285 Excessive number of connected Green Error code Content indoor units (more than 17 units) Remote control: Keeps flashing Stays OFF Indoor by controlling with one remote control 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are more than 17 indoor units connected to one Defective remote control remote control?
  • Page 103: Address Setting Error Of Indoor Units

    '20 • SR-SM-285 Green Error code Content Address setting error of Remote control: indoor units Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure E11 occurs Is “Master IU address set” function of remote 2. Error detection method control used? IU address has been set using the “Master IU address set”...
  • Page 104: Indoor Fan Motor Anomaly

    '20 • SR-SM-285 Green Error code Content Indoor fan motor anomaly Remote control: Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Does any foreign material Remove foreign material. intervene in rotational area of fan propeller? Does the fan 2.
  • Page 105: E19 Indoor Unit Operation Check, Drain Pump Motor Check Setting Error

    '20 • SR-SM-285 Green Error code Content Indoor unit operation check, Remote control: drain pump moter check setting error Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure E19 occurs when the power ON Is SW7-1 Defective indoor unit on the indoor unit control PCB ON ?
  • Page 106: Indoor Fan Motor Rotation Speed Anomaly

    '20 • SR-SM-285 Green Error code Content Indoor fan motor rotation Remote control: speed anomaly Keeps flashing 1-time flash Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Does any foreign material Remove foreign material. intervene in rotational area of fan propeller? Does the fan 2.
  • Page 107 '20 • SR-SM-285 Green Error code Content Remote control Remote control: temperature sensor anomaly Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the remote Correct. ➞ Insert connector control temperature sensor connected properly? securely.
  • Page 108 '20 • SR-SM-285 Green Error code Content Cooling overload operation Remote control: Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure * For the characteristics of outdoor heat exchanger temperature Are the sensor, refer to E37. characteristics of outdoor heat exchanger Replace outdoor heat...
  • Page 109 '20 • SR-SM-285 Green Error code Content Discharge pipe temperature error Remote control: Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure * For the characteristics of discharge Are the pipe temperature sensor, refer to E39. characteristics of Replace discharge pipe discharge pipe temperature...
  • Page 110 '20 • SR-SM-285 Green Error code Content Outdoor heat exchanger Remote control: temperature sensor anomaly Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the outdoor heat exchanger temperature Correct connector. sensor connector connected properly? 2.
  • Page 111 '20 • SR-SM-285 Green Error code Content Outdoor air temperature Remote control: sensor anomaly Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure the outdoor air Correct connector. temperature sensor connector connected properly? For the characteristics of outdoor air temperature sensor, see the following graph.
  • Page 112 '20 • SR-SM-285 Green Error code Content Discharge pipe Remote control: temperature sensor anomaly Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model Diagnosis Countermeasure All models Is the discharge pipe temperature sensor Correct connector. connector connected properly? 2. Error detection method For the characteristics of discharge pipe Are the temperature sensor, see the following graph.
  • Page 113 '20 • SR-SM-285 Green Error code Content Service valve (gas side) closing operation Remote control: Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Are the Open the service valve. service valve (gas side) opened? 2.
  • Page 114 '20 • SR-SM-285 Green Error code Content Current cut (1/2) Remote control: Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the Power source Check power source. voltage OK? 2. Error detection method Are the Open the valves.
  • Page 115 inverter PCB 1-time flash '20 • SR-SM-285 Green Error code Content Current cut (2/2) Remote control: Keeps flashing Stays OFF Indoor 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure From previous page Is the checked result of power Defective outdoor unit transistor module PCB ➞...
  • Page 116 '20 • SR-SM-285 Green Error code Content Remote control: Active filter voltage error Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Restore normal condition. Is the power source normal? 2. Error detection method Is voltage Restore normal condition.
  • Page 117: E48 Outdoor Fan Motor Anomaly

    '20 • SR-SM-285 Green Error code Content Outdoor fan motor anomaly Remote control: Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Does any foreign material intervene Remove foreign matter. in rotational area of fan propeller? Does the 2.
  • Page 118 '20 • SR-SM-285 Green Green Error code Error code Content Content Power transistor error Power transistor anomaly Remote controller: E51 Remote control: Indoor Keeps flashing Stays OFF Keeps flashing Stays Off Indoor (Models SRC50, 60) 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure...
  • Page 119: Are The Characteristics Of

    '20 • SR-SM-285 Green Error code Content Insufficient refrigerant amount Remote control: or detection of service valve closure Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the Open fully. service valve fully opened? Are the connections of indoor heat exchanger and/or return air...
  • Page 120 '20 • SR-SM-285 Green Error code Green Content Error code Content Current safe stop Current safe stop Keeps flashing Stays Off Indoor Remote controller: E58 Remote control: Indoor Keeps flashing Stays OFF (Model SRC50, 60) 3 time flash Outdoor ― 5.
  • Page 121 '20 • SR-SM-285 Green Error code Content Compressor startup failure Remote control: Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Disconnect the outdoor fan motor Compressor does not start at all. connector and try to startup. Neither noise nor vibration cannot be heard.
  • Page 122 '20 • SR-SM-285 Green Error code Content Compressor rotor lock error Remote control: Indoor Keeps flashing Stays OFF 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Is the Check and correct the power source voltage power source voltage. Reset the power source and restart operation. 2.
  • Page 123 '20 • SR-SM-285 3. ELECTRICAL WIRING (1) Indoor units (a) Ceiling concealed type (SRR)   Models SRR25ZS-W, 35ZS-W RJJ000Z003...
  • Page 124 '20 • SR-SM-285 (b) 4-way ceiling cassette type (FDTC)   Models FDTC25VH1, 35VH1 PJF000Z516...
  • Page 125 '20 • SR-SM-285 (2) Outdoor units   Models SRC25ZS-W1, 35ZS-W1 RWC000Z315...
  • Page 126: Temperature (°C)

    '09•SRK-DB-087D '20 • SR-SM-285 4. PIPING SYSTEM 5 PIPING SYSTEM   Models SRR25ZS-W, 35ZS-W Models SRK20ZS-S, 25ZS-S FDTC25VH1, 35VH1 Heat exchanger temperature sensor (Th2 , Thi-R3) pipe temperature temperature (Th1,Thi-A) (Th2 , Thi-R1) 4-way valve Humidity sensor (HS) temperature (Thi-R2)
  • Page 127 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. 2-3, Marunouchi 3-chome, Chiyoda-ku, Tokyo, 100-8332, Japan http://www.mhi-mth.co.jp/en/ Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.