Inspection Of Parts (Outdoor Unit) - Sanyo Mini ECO-i CHXR03652 Service Manual

Table of Contents

Advertisement

5. Inspection of Parts (Outdoor Unit)

(1)
Electronic control valve (MOV1)
MOV1: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN41 connector (6P, white)
on the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used.
Set the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)
If the voltage is normal, measure the resistance between connector pin 5 and pins 1 through 4.
Resistance between pin 5 and pins 1 through 4 should be approximately 46
or
, then replace the coil.)
(2)
Crankcase heater
Connect a clamp meter to 1 of the 2 crankcase heater wires and measure the current. The current is
normal if the result is 0.15 A or higher.
(As a guide, the current should be 0.14 A (180 V) – 0.17 A (220 V).)
Test Pin
When the test pin on the outdoor unit main control PCB is short-circuited, each part can be operated individually.
After turning OFF the outdoor unit power, short circuit the test pin (CN44, white), then turn the power back ON.
The following operations will start after turning ON the outdoor unit power when the test pin (CN44, white) is
1
short-circuited.
(1)
Set DC fan motor at W5 (FM1 : 340 – 360 rpm, FM2 : 360 – 380 rpm).
(2)
20S turns ON for 0.5 sec.
(3)
Check Inter-unit control wiring circuit.
2
If normal state, go to the next step. If not, it stops after LED1 starts blinking at 0.5 sec intervals and LED2
turns off.
(4)
Connector CH1 turns ON for 0.5 sec.
(5)
Do the test to read / write EEPROM.
If normal state, go to the next step. If not, it stops after LED1 starts blinking at 0.5 sec intervals and LED2
3
lights.
(6)
Connector O
2
(7)
Check inter-outdoor unit control wiring circuit to outdoor unit maintenance remote controller.
If normal state, go to the next step. If not, it stops after LED1 turns off and LED2 starts blinking at 0.5 sec
4
intervals.
(8)
LED1 turns ON for 0.5 sec.
(9)
Do the test(1) of circuit for writing micro-computing software.
If normal state, go to the next step. If not, it stops after LED1 starts blinking and LED2 starts blinking at 0.5
sec intervals.
5
(10)
LED2 turns ON for 0.5 sec.
(11)
Do the test(2) of circuit for writing micro-computing software.
If normal state, go to the next step. If not, it stops after LED1 starts blinking and LED2 starts blinking at 0.5
sec intervals.
6
(12)
Outputs listed below turn ON for 0.5 sec.
No.
Contents of output
1
MOV1 – A
2
MOV1 – B
3
MOV1 – / A
4
MOV1 – / B
5
turns ON for 0.5 sec.
5 - 18
Mini ECO-i SYSTEM
Trouble Diagnosis
for all. (If the result is 0

Advertisement

Table of Contents
loading

Table of Contents